Mini design project

Pump room control panel

Duty/standby VFD pumps and a jockey pump: motor currents, incomer by operating mode, feeders, control philosophy and commissioning.

Teaching project. A complete preliminary design method with typical values — not a design to build from.

2 × 22 kWduty / standby pumps on VFDs
40.6 Afull-load current of each main pump
63 Aincomer for duty/standby
125 Aincomer if duty/assist is required

The brief

A water pump room has two 22 kW pumps (duty/standby, VFD controlled), one 3 kW jockey pump (direct-on-line) and about 2 kW of auxiliaries (lighting, sockets, panel heater, 24 V control). Design the motor control panel: currents, incomer, feeders, cables and the control philosophy.

Teaching example. Motor data, VFD sizing and cable sizes must come from the actual manufacturer data and the applicable standards. Confirm the operating mode (duty/standby vs duty/assist) with the mechanical designer — it changes the incomer.

Step 1 — Motor currents

I = P ÷ (√3 · V · η · cos φ)
Main pump: 22 000 ÷ (1.732 × 400 × 0.92 × 0.85) = 40.6 A
Jockey: 3 000 ÷ (1.732 × 400 × 0.85 × 0.82) = 6.2 A

Auxiliaries: 2 kW single-phase ≈ 8.7 A on one phase (≈ 2.9 A when spread over three phases).

Step 2 — Maximum demand and incomer

Maximum demand by operating mode
ModeRunning at the same timeCurrentIncomer (≈ +15 %)
Duty / standby1 main pump + jockey + aux49.7 A63 A
Duty / assist2 main pumps + jockey + aux90.3 A125 A

The incoming cable and the upstream SMDB feeder must be sized for the chosen mode. VFDs reduce starting current, so the incomer does not need to cover DOL starting of the main pumps.

Step 3 — Feeders

Outgoing circuits (typical — verify)
CircuitProtectionSwitching / controlCable
Pump P-1MCCB 63 A (or fuses per VFD manual)VFD rated ≥ 41 A for the motor and duty4c 16 mm² screened, 360° glands
Pump P-2MCCB 63 AVFD, as P-14c 16 mm² screened
Jockey J-1Motor protection circuit breaker set to 6.2 ADOL contactor4c 2.5 mm²
LightingMCB B10 + 30 mA RCD—2c+E 1.5 mm²
SocketsMCB B16 + 30 mA RCD—2c+E 2.5 mm²
Panel heaterMCB B6Thermostat / hygrostat2c+E 1.5 mm²
24 V DC controlMCB C6PSU with healthy contact—

Check each motor cable for current rating, voltage drop and — for VFDs — the drive manufacturer's maximum cable length and EMC requirements.

Step 4 — Control philosophy

Auto start/stop

Duty pump starts on low pressure (or low level setpoint) and stops on high; jockey keeps pressure between demands.

Duty rotation

Duty and standby swap every start or every 24 h so wear is even.

Standby on fault

VFD fault or no-flow on the duty pump starts the standby automatically and raises an alarm.

Dry-run protection

Low-level switch in the tank stops all pumps and alarms — hard-wired, not only in the PLC.

Local / remote

Hand-Off-Auto selector per pump; emergency stop at the panel.

Signals to SCADA

Running, tripped, auto/manual, pressure, level, VFD speed and fault code.

Step 5 — Testing before handover

Pump panel commissioning

0 / 6
Ticks are saved only in this browser. Adapt the list to the approved ITP and manufacturer instructions; it does not define acceptance criteria.
Single-line diagram of the example pump room panel (preliminary)
Figure 5.Single-line diagram of the example pump room panel (preliminary).

Try it yourself

Change the loads and rebuild the board in the SLD builder, size the cables with the cable sizing assistant and estimate quantities with the quantity estimator.