Mini design project
Pump room control panel
Duty/standby VFD pumps and a jockey pump: motor currents, incomer by operating mode, feeders, control philosophy and commissioning.
Teaching project. A complete preliminary design method with typical values — not a design to build from.
The brief
A water pump room has two 22 kW pumps (duty/standby, VFD controlled), one 3 kW jockey pump (direct-on-line) and about 2 kW of auxiliaries (lighting, sockets, panel heater, 24 V control). Design the motor control panel: currents, incomer, feeders, cables and the control philosophy.
Teaching example. Motor data, VFD sizing and cable sizes must come from the actual manufacturer data and the applicable standards. Confirm the operating mode (duty/standby vs duty/assist) with the mechanical designer — it changes the incomer.
Step 1 — Motor currents
Main pump: 22 000 ÷ (1.732 × 400 × 0.92 × 0.85) = 40.6 A
Jockey: 3 000 ÷ (1.732 × 400 × 0.85 × 0.82) = 6.2 A
Auxiliaries: 2 kW single-phase ≈ 8.7 A on one phase (≈ 2.9 A when spread over three phases).
Step 2 — Maximum demand and incomer
| Mode | Running at the same time | Current | Incomer (≈ +15 %) |
|---|---|---|---|
| Duty / standby | 1 main pump + jockey + aux | 49.7 A | 63 A |
| Duty / assist | 2 main pumps + jockey + aux | 90.3 A | 125 A |
The incoming cable and the upstream SMDB feeder must be sized for the chosen mode. VFDs reduce starting current, so the incomer does not need to cover DOL starting of the main pumps.
Step 3 — Feeders
| Circuit | Protection | Switching / control | Cable |
|---|---|---|---|
| Pump P-1 | MCCB 63 A (or fuses per VFD manual) | VFD rated ≥ 41 A for the motor and duty | 4c 16 mm² screened, 360° glands |
| Pump P-2 | MCCB 63 A | VFD, as P-1 | 4c 16 mm² screened |
| Jockey J-1 | Motor protection circuit breaker set to 6.2 A | DOL contactor | 4c 2.5 mm² |
| Lighting | MCB B10 + 30 mA RCD | — | 2c+E 1.5 mm² |
| Sockets | MCB B16 + 30 mA RCD | — | 2c+E 2.5 mm² |
| Panel heater | MCB B6 | Thermostat / hygrostat | 2c+E 1.5 mm² |
| 24 V DC control | MCB C6 | PSU with healthy contact | — |
Check each motor cable for current rating, voltage drop and — for VFDs — the drive manufacturer's maximum cable length and EMC requirements.
Step 4 — Control philosophy
Auto start/stop
Duty pump starts on low pressure (or low level setpoint) and stops on high; jockey keeps pressure between demands.
Duty rotation
Duty and standby swap every start or every 24 h so wear is even.
Standby on fault
VFD fault or no-flow on the duty pump starts the standby automatically and raises an alarm.
Dry-run protection
Low-level switch in the tank stops all pumps and alarms — hard-wired, not only in the PLC.
Local / remote
Hand-Off-Auto selector per pump; emergency stop at the panel.
Signals to SCADA
Running, tripped, auto/manual, pressure, level, VFD speed and fault code.
Step 5 — Testing before handover
Pump panel commissioning
0 / 6Try it yourself
Change the loads and rebuild the board in the SLD builder, size the cables with the cable sizing assistant and estimate quantities with the quantity estimator.