Engineering glossary

Short definitions of terms and abbreviations used across the departments, guides and calculators.

ACB
Air circuit breaker — large LV breaker typically used as transformer incomer or main feeder device.
Adiabatic equation
S = √(I²t)/k; estimates minimum conductor size to withstand a short-circuit without exceeding its final temperature.
ATS
Automatic transfer switch — transfers load between normal and standby supplies.
Bonding (protective equipotential)
Connecting conductive parts together so they stay at similar potential during a fault.
Buchholz relay
Gas/oil-surge protection device fitted between tank and conservator on conservator-type transformers.
Cascading
Use of an upstream current-limiting device to allow a downstream device of lower breaking capacity, for manufacturer-tested combinations.
CPC
Circuit protective conductor — connects exposed-conductive-parts to the main earthing terminal.
CT
Current transformer — scales primary current down for protection and metering.
DAR
Dielectric absorption ratio — IR at 60 s divided by IR at 30 s.
Demand factor
Ratio of maximum demand to connected load for a group of loads.
Differential protection (87)
Unit protection comparing currents entering and leaving a protected zone.
DMZ
Demilitarised zone — network segment that brokers data between IT and OT networks.
Dyn11
Transformer vector group: HV delta, LV star with neutral; clock 11 = 330° lag, i.e. LV leads HV by 30°.
Earth electrode
Conductive part in contact with the earth, such as a rod, tape, plate or grid.
EPR / GPR
Earth (ground) potential rise — rise of earthing-system potential during an earth fault.
FAT / SAT
Factory and site acceptance tests of equipment and control systems.
Feeder pillar
Outdoor enclosure with protection, control and metering for street lighting or LV distribution circuits.
FPI
Fault passage indicator — shows whether fault current passed through an MV circuit.
Grading margin
Time difference between operation of upstream and downstream protection at a given fault current.
IAC
Internal arc classification of MV switchgear, describing personnel protection during an internal arc.
Icu / Ics
Ultimate and service short-circuit breaking capacities of an LV circuit breaker.
Icw
Rated short-time withstand current (with duration) of switchgear or an assembly.
IDMT
Inverse definite minimum time — overcurrent characteristic that operates faster at higher currents.
IED
Intelligent electronic device — microprocessor-based protection/control device.
Insulation resistance (IR)
Resistance of insulation measured with a DC test voltage.
ITP
Inspection and test plan listing inspections, tests, criteria, records and hold/witness points.
LBS
Load-break switch — can make and break load current but not interrupt fault current.
Loop check
Verification of an instrument or control signal from field device to control system and HMI.
MCC
Motor control centre — assembly of motor starters and feeders.
MET
Main earthing terminal — where earthing, protective and bonding conductors connect.
MIR / WIR
Material and work inspection requests used to call for inspection on site.
NCR
Non-conformance report — records work or material that does not meet requirements.
NOP
Normally-open point — the open switch that splits an MV ring into two radial feeders.
ONAN
Transformer cooling code: oil natural, air natural.
PEN
Combined protective earth and neutral conductor (TN-C portions of a system).
PI
Polarisation index — IR at 10 minutes divided by IR at 1 minute.
PLC
Programmable logic controller.
Power factor
Ratio of active power to apparent power (cos φ for sinusoidal conditions).
RCD
Residual current device — detects imbalance between line and neutral currents (earth leakage).
REF
Restricted earth-fault protection for transformer windings.
RFI
Request for information — formal query to the designer.
RMU
Ring main unit — compact MV switchgear for ring networks.
SCADA
Supervisory control and data acquisition.
Selectivity (discrimination)
Coordination so that only the protective device nearest a fault operates.
SLD
Single-line diagram representing a three-phase system with one line per circuit.
Soft starter
Thyristor-based reduced-voltage motor starter.
Step / touch voltage
Voltages experienced between feet, or between hand and feet, during an earth fault.
TMS
Time multiplier setting of an IDMT relay.
TN-C-S / TN-S / TT
LV system earthing arrangements describing source and exposed-part earthing.
VFD
Variable frequency drive — controls motor speed by varying supply frequency and voltage.
VLF test
Very-low-frequency AC withstand/diagnostic test used on MV cables.
VPIS
Voltage presence indicating system on MV switchgear (indication only).
Z% (impedance voltage)
Transformer short-circuit impedance as a percentage; governs fault level and regulation.