Reference

Electrical formula sheet.

The formulas used across the hub on one printable page — each linked to its calculator.

Power & current

Single-phase powerP = V · I · cos φV phase voltageCalculator →
Three-phase powerP = √3 · V_L · I_L · cos φV_L line-to-lineCalculator →
Apparent powerS = √(P² + Q²) ; S = √3 · V_L · I_LkVACalculator →
Reactive powerQ = P · tan φkvarCalculator →
Power factorPF = cos φ = P ÷ SCalculator →
Star connectionV_L = √3 · V_ph ; I_L = I_ph
Delta connectionV_L = V_ph ; I_L = √3 · I_ph
Neutral current (equal PF)I_N = √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁)no harmonics

Transformers

Turns ratioV₁ ÷ V₂ = N₁ ÷ N₂ = I₂ ÷ I₁ideal transformer
Rated currentI = S ÷ (√3 · V)per sideCalculator →
Fault current (infinite source)I_sc ≈ I_rated × 100 ÷ Z%upper boundCalculator →
Impedance in ohms (LV)Z = Z% ÷ 100 × V² ÷ SCalculator →

Cables

Derated ratingIz = It × Ca × Cg × Cifactors from tablesCalculator →
CoordinationIb ≤ In ≤ IzCalculator →
Voltage drop (3-phase)ΔV = √3 · I · L · (R cos φ + X sin φ)L in km, R & X in Ω/kmCalculator →
Voltage drop (1-phase)ΔV = 2 · I · L · (R cos φ + X sin φ)Calculator →
Short-circuit withstandS ≥ √(I² t) ÷ kk ≈ 143 Cu-XLPE, 115 Cu-PVCCalculator →
Resistance vs temperatureR₂ = R₁ · [1 + α (T₂ − T₁)]α ≈ 0.00393 /°C copper

Short circuit

Three-phase faultI_k3 = c · V ÷ (√3 · |Z|)c ≈ 1.05–1.10 (LV, IEC 60909 c_max)Calculator →
Per-unit impedance change of basez_new = z_old × (S_new ÷ S_old) × (V_old ÷ V_new)²
Source impedanceZ_s = c · V² ÷ S_scCalculator →

Protection

IEC standard inverset = TMS × 0.14 ÷ (M^0.02 − 1)M = I ÷ IsCalculator →
IEC very inverset = TMS × 13.5 ÷ (M − 1)Calculator →
IEC extremely inverset = TMS × 80 ÷ (M² − 1)Calculator →
CT burdenVA = I² × (R_relay + R_leads)check against CT rating

Motors

Full-load currentI = P_out ÷ (√3 · V · η · cos φ)Calculator →
Synchronous speedn_s = 120 · f ÷ pp = number of polesCalculator →
Slips = (n_s − n) ÷ n_sCalculator →
TorqueT = 9550 · P(kW) ÷ n(rpm)N·m
Affinity laws (pumps/fans)Q ∝ n ; H ∝ n² ; P ∝ n³approximate

Earthing

Single rod (Dwight)R = ρ ÷ (2πL) · [ln(8L ÷ d) − 1]Calculator →
Earth fault loopZs = Ze + (R₁ + R₂)
Fault currentI_f = U₀ ÷ Zs

Lighting & energy

Lumen methodN = E · A ÷ (F · UF · MF)
EnergyE (kWh) = P (kW) × t (h)
Capacitor kvarQ_c = P · (tan φ₁ − tan φ₂)Calculator →

Instrumentation & testing

4–20 mA scalingValue = LRV + (I − 4) ÷ 16 × (URV − LRV)Calculator →
Polarisation indexPI = R₁₀ min ÷ R₁ minCalculator →
Dielectric absorption ratioDAR = R₆₀ s ÷ R₃₀ sCalculator →