Reference
Electrical formula sheet.
The formulas used across the hub on one printable page — each linked to its calculator.
Power & current
| Single-phase power | P = V · I · cos φ | V phase voltage | Calculator → |
| Three-phase power | P = √3 · V_L · I_L · cos φ | V_L line-to-line | Calculator → |
| Apparent power | S = √(P² + Q²) ; S = √3 · V_L · I_L | kVA | Calculator → |
| Reactive power | Q = P · tan φ | kvar | Calculator → |
| Power factor | PF = cos φ = P ÷ S | Calculator → | |
| Star connection | V_L = √3 · V_ph ; I_L = I_ph | ||
| Delta connection | V_L = V_ph ; I_L = √3 · I_ph | ||
| Neutral current (equal PF) | I_N = √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁) | no harmonics |
Transformers
| Turns ratio | V₁ ÷ V₂ = N₁ ÷ N₂ = I₂ ÷ I₁ | ideal transformer | |
| Rated current | I = S ÷ (√3 · V) | per side | Calculator → |
| Fault current (infinite source) | I_sc ≈ I_rated × 100 ÷ Z% | upper bound | Calculator → |
| Impedance in ohms (LV) | Z = Z% ÷ 100 × V² ÷ S | Calculator → |
Cables
| Derated rating | Iz = It × Ca × Cg × Ci | factors from tables | Calculator → |
| Coordination | Ib ≤ In ≤ Iz | Calculator → | |
| Voltage drop (3-phase) | ΔV = √3 · I · L · (R cos φ + X sin φ) | L in km, R & X in Ω/km | Calculator → |
| Voltage drop (1-phase) | ΔV = 2 · I · L · (R cos φ + X sin φ) | Calculator → | |
| Short-circuit withstand | S ≥ √(I² t) ÷ k | k ≈ 143 Cu-XLPE, 115 Cu-PVC | Calculator → |
| Resistance vs temperature | R₂ = R₁ · [1 + α (T₂ − T₁)] | α ≈ 0.00393 /°C copper |
Short circuit
| Three-phase fault | I_k3 = c · V ÷ (√3 · |Z|) | c ≈ 1.05–1.10 (LV, IEC 60909 c_max) | Calculator → |
| Per-unit impedance change of base | z_new = z_old × (S_new ÷ S_old) × (V_old ÷ V_new)² | ||
| Source impedance | Z_s = c · V² ÷ S_sc | Calculator → |
Protection
| IEC standard inverse | t = TMS × 0.14 ÷ (M^0.02 − 1) | M = I ÷ Is | Calculator → |
| IEC very inverse | t = TMS × 13.5 ÷ (M − 1) | Calculator → | |
| IEC extremely inverse | t = TMS × 80 ÷ (M² − 1) | Calculator → | |
| CT burden | VA = I² × (R_relay + R_leads) | check against CT rating |
Motors
| Full-load current | I = P_out ÷ (√3 · V · η · cos φ) | Calculator → | |
| Synchronous speed | n_s = 120 · f ÷ p | p = number of poles | Calculator → |
| Slip | s = (n_s − n) ÷ n_s | Calculator → | |
| Torque | T = 9550 · P(kW) ÷ n(rpm) | N·m | |
| Affinity laws (pumps/fans) | Q ∝ n ; H ∝ n² ; P ∝ n³ | approximate |
Earthing
| Single rod (Dwight) | R = ρ ÷ (2πL) · [ln(8L ÷ d) − 1] | Calculator → | |
| Earth fault loop | Zs = Ze + (R₁ + R₂) | ||
| Fault current | I_f = U₀ ÷ Zs |
Lighting & energy
| Lumen method | N = E · A ÷ (F · UF · MF) | ||
| Energy | E (kWh) = P (kW) × t (h) | ||
| Capacitor kvar | Q_c = P · (tan φ₁ − tan φ₂) | Calculator → |
Instrumentation & testing
| 4–20 mA scaling | Value = LRV + (I − 4) ÷ 16 × (URV − LRV) | Calculator → | |
| Polarisation index | PI = R₁₀ min ÷ R₁ min | Calculator → | |
| Dielectric absorption ratio | DAR = R₆₀ s ÷ R₃₀ s | Calculator → |
Electrical Engineering Hub · electricalengineeringhub.com · Formulas are standard engineering relationships; values and limits for design come from the applicable standards and manufacturer data.