Cables are the longest-lived and least visible assets in a distribution network. A cable that is correctly selected, carefully installed, properly jointed and tested will outlast most of the equipment it connects; a poorly made joint can fail within months.
What this department covers
- MV and LV cable construction
- Selection and sizing checks
- Installation methods and derating
- Pulling, bending and handling
- MV joints and terminations
- Screen bonding
- Testing before and after energisation
01Cable construction
An MV cable is an insulation system as much as a conductor. Around the stranded copper or aluminium conductor sit a semi-conductive conductor screen, the main insulation (commonly XLPE or EPR), a semi-conductive insulation screen, a metallic screen of copper wires or tape, and protective layers — bedding, armour where specified, and an oversheath. The semi-conductive layers keep the electric field radial and free of air voids at the insulation boundaries; the metallic screen carries capacitive charging current and earth-fault current and must be bonded and continuous.
LV cables are simpler — insulated cores (PVC or XLPE), often laid up as multicore with or without armour (steel wire armour for multicore, aluminium wire armour or no armour for single-core AC to avoid induced heating in magnetic armour) and an oversheath. Fire-performance cables (low smoke zero halogen, fire-resistant) are specified by the project where life-safety or building requirements demand them.
| Element | Function | Review point |
|---|---|---|
| Conductor (Cu / Al, class) | Carries load current | Material and cross-section vs design; compatible lugs/connectors (Al needs suitable fittings) |
| Insulation (XLPE, EPR, PVC) | Withstands voltage; sets maximum conductor temperature | Voltage designation; temperature limits used in rating calculations |
| Semi-conductive screens | Field control at conductor and insulation surfaces | Bonded vs strippable type — affects jointing kit choice |
| Metallic screen | Earth-fault current path; field confinement | Cross-section adequate for earth-fault current and duration |
| Armour | Mechanical protection; may form part of protective conductor | Magnetic armour not used on single-core AC circuits |
| Oversheath | Moisture and mechanical protection | Material per environment (PE, PVC, LSZH); termite/UV requirements if specified |
02Selection and sizing — the six checks
No cable is selected on current alone. A sound selection satisfies every one of these checks at the same time, and the result is the largest cross-section any of them requires.
- Voltage designation.The cable's rated voltage (U₀/U and Um) suits the system nominal and highest voltage and its earthing arrangement.
- Continuous current rating.Using manufacturer or standard rating data for the actual construction and installation method, corrected for ambient/ground temperature, soil thermal resistivity, depth, grouping and ducts.
- Voltage drop.Under maximum design current, and for motors also during starting, within the project's limits.
- Short-circuit thermal withstand.Conductor (and screen) withstand the prospective fault current for the protection clearing time.
- Earth-fault performance.On LV, the earth-fault loop impedance allows the protective device to disconnect within the required time; on MV, screen capacity is adequate.
- Installation and compatibility.Bending radius, pulling tension, termination space, gland sizes, lug compatibility and route constraints.
| Factor | Effect | Where it comes from |
|---|---|---|
| Higher ground/ambient temperature | Less temperature headroom → lower rating | Site data and project design basis |
| Higher soil thermal resistivity | Heat cannot escape → lower rating | Soil survey; thermal backfill may be specified |
| Grouping / reduced spacing | Mutual heating between circuits | Route design; rating factors for the arrangement |
| Installation in ducts | Air gap adds thermal resistance | Duct sizing and fill; manufacturer duct ratings |
| Greater burial depth | Slightly lower rating (and better mechanical protection) | Approved trench detail |
| Solar radiation (above ground) | Additional heat gain | Exposed routes, trays on rooftops |
The adiabatic equation gives a quick check of conductor short-circuit withstand. It assumes all heat is retained in the conductor during the fault, which is reasonable for short durations.
03Installation: handling, pulling and bending
Most installation defects are mechanical: insulation damaged by sharp bends, sheaths scuffed during pulling, water entering cut ends, or cables crushed in poorly prepared trenches. The manufacturer's limits for pulling tension, sidewall pressure and minimum bending radius govern; the radius is normally stated as a multiple of the cable's overall diameter and is larger during pulling than for the final set position.
- Inspect drums on receipt.Check drum and cable identification against the approved submittal, look for drum damage, confirm cap seals on both ends and record lengths.
- Prepare the route.Trench excavated to the approved depth and width, bottom levelled and free of stones, bedding laid; ducts proven clear with a mandrel; road crossings and service crossings protected.
- Plan the pull.Drum position, direction, rollers at bends and entries, pulling method (stocking or eye), dynamometer where tensions are significant, communication between ends.
- Pull and lay.Pull at steady speed within tension limits; keep bending radius above the minimum; maintain formation (trefoil/flat) and spacing per design; avoid crossings within the formation.
- Seal and protect.Re-seal cut ends immediately; install cover tiles, warning tape and backfill per detail; record route and depth for as-builts.
- Test before backfillingwhere the ITP requires (commonly an oversheath or insulation resistance test) to catch damage while it is still accessible.
Never leave MV cable ends unsealed. Moisture entering the conductor or screen can migrate along the cable and cause premature insulation failure long after energisation.
04MV joints and terminations
A joint must rebuild every functional layer of the cable across the connection: conductor continuity through a connector, insulation thickness, stress control at the screen cut, the semi-conductive outer layer, metallic screen continuity and the outer protection. Terminations do the same at the end of the cable, with stress control and — outdoors — additional creepage distance via sheds.
| Stage | Critical control | Typical defect if missed |
|---|---|---|
| Kit selection | Kit matches cable type, voltage, conductor size and screen type | Wrong stress control; poor fit; early failure |
| Environment | Dry, clean, sheltered work area; tools clean; hands/gloves clean | Contamination at insulation interface → tracking |
| Cut-back dimensions | Exactly per kit instructions, measured and marked | Stress concentration; insufficient creepage |
| Screen removal | Square cut, no nicks into insulation, all semi-con removed where required | Partial discharge at screen edge |
| Insulation surface | Smooth, no scores, cleaned with approved solvent in the correct direction | Voids/tracking paths |
| Connector | Correct lug/connector type and die; shear-bolts fully sheared; edges smoothed | Hot joints; field enhancement at sharp edges |
| Screen continuity | Screen connector/mesh applied and secured | Loss of earth-fault path; induced voltage hazards |
| Recording | Jointer name/competency, kit batch, date, location, photos at hold points | No traceability when investigating failures |
05Screen bonding and induced voltages
For single-core MV cables, current in the conductor induces voltage in the metallic screen. If screens are bonded to earth at both ends, circulating currents flow and add losses that reduce the cable rating; if bonded at one end only, a standing voltage appears at the open end and must be limited and protected. Long high-current circuits sometimes use cross-bonding. The bonding method is a design decision that affects rating, safety and earthing — it must be shown on the drawings and installed exactly as designed.
06Testing cables
Typical cable tests include insulation resistance, continuity and phasing, oversheath integrity (where specified), and for MV cables an after-installation withstand test — commonly a very-low-frequency (VLF) AC test or another method specified by the project or utility (DC withstand testing is generally discouraged for XLPE insulation by many references) — sometimes with partial-discharge or tan δ diagnostics. The test method, voltage, duration and acceptance criteria are those of the approved ITP, the cable/accessory manufacturer and the applicable standard; they are not universal.
Cable tests use hazardous voltages and long cables store significant charge. Apply the permit system, barrier the far end, and discharge and earth the cable after every test.
07Troubleshooting
| Symptom | Likely causes | Checks |
|---|---|---|
| Low insulation resistance on one core | Sheath/insulation damage, moisture at an end, contaminated termination | Sectionalise; clean and re-test terminations; check end caps; locate fault if persistent |
| Joint failure soon after energisation | Workmanship (contamination, cut-back error), wrong kit | Failure investigation with jointing records and photos; review competency and kit |
| Cable hot under load | Overload, grouping, poor thermal backfill, both-end bonding on high-current single-core | Load logging; compare with rating basis; check bonding arrangement |
| Nuisance earth-fault trips | Damaged insulation, moisture, long cable capacitive leakage | IR test; check earth-fault settings vs charging current |
| Voltage drop complaints | Undersized cable, longer route than designed | Compare as-built length; recalculate with actual load |
Cable installation & jointing inspection
0 / 13- Before laying
- During laying
- Jointing & termination
- Close-out