Given: A balanced three-phase load takes 50 kW at 400 V (line-to-line) and power factor 0.85 lagging.
Find: Line current, apparent power and reactive power.
Try it first — your answer (A): Check
1 Choose the formulaFor a balanced three-phase load, P = √3 · V_L · I_L · cos φ.
2 Rearrange for currentI = P ÷ (√3 · V · cos φ) I = 50,000 ÷ (1.732 × 400 × 0.85) = 84.9 A
3 Apparent powerS = P ÷ cos φ = 50 ÷ 0.85 = 58.8 kVA
4 Reactive powerQ = √(S² − P²) = √(58.8² − 50²) = 31.0 kvar
Answer: I ≈ 84.9 A, S ≈ 58.8 kVA, Q ≈ 31.0 kvar
Given: Three identical impedances of 10 Ω at 30° (inductive) are connected to a 400 V three-phase supply, first in star, then in delta.
Find: Line current and total power in each connection.
Try it first — your answer (A): Check
1 Star: phase voltageIn star each impedance sees the phase voltage.
V_ph = 400 ÷ √3 = 230.9 V
2 Star: currentI_L = I_ph = 230.9 ÷ 10 = 23.09 A
3 Star: powerP = 3 · V_ph · I_ph · cos 30° = 3 × 230.9 × 23.09 × 0.866 = 13.86 kW
4 Delta: phase currentIn delta each impedance sees the full line voltage.
I_ph = 400 ÷ 10 = 40.0 A
5 Delta: line currentI_L = √3 · I_ph = 69.3 A
6 Delta: power and comparisonP = 3 × 400 × 40.0 × 0.866 = 41.57 kW
Delta draws 3× the line current and 3× the power of star — the basis of star-delta motor starting.
Answer: Star: 23.1 A, 13.86 kW · Delta: 69.3 A, 41.57 kW (delta line current)
Show step 1 Show full solution
Given: A 1000 kVA, 11/0.4 kV three-phase distribution transformer.
Find: Rated current on the HV and LV sides.
Try it first — your answer (A): Check
2 HV sideI_HV = 1,000,000 ÷ (1.732 × 11 000) = 52.5 A
3 LV sideI_LV = 1,000,000 ÷ (1.732 × 400) = 1,443 A
4 Check with the ratioThe current ratio is the inverse of the voltage ratio: 1,443 ÷ 52.5 ≈ 27.5 = 11 000 ÷ 400 = 27.5 ✓
Answer: I_HV ≈ 52.5 A, I_LV ≈ 1,443 A (LV side)
Given: An 11 kV source with a fault level of 250 MVA feeds a 1000 kVA, 6 % impedance, 11/0.4 kV transformer. Use a 10 MVA base. Ignore resistance and cable impedance.
Find: Three-phase fault current at the transformer LV terminals.
Try it first — your answer (kA): Check
1 Source impedance on the basez_s = S_base ÷ S_fault = 10 ÷ 250 = 0.040 pu
2 Transformer impedance on the basez_t = z% × (S_base ÷ S_rated) = 0.06 × (10 ÷ 1) = 0.60 pu
3 Total impedance to the faultz = 0.040 + 0.60 = 0.640 pu
4 Fault MVAS_f = S_base ÷ z = 10 ÷ 0.640 = 15.62 MVA
5 Fault current at 400 VI_k = S_f ÷ (√3 · V) = 15,625,000 ÷ (1.732 × 400) = 22.55 kA
Without the source impedance (infinite bus) it would be 1443 ÷ 0.06 = 24.06 kA — the source reduces it a little.
Answer: I_k ≈ 22.55 kA
Given: A feeder carries 120 A at PF 0.85 over 80 m of cable with R = 0.494 Ω/km and X = 0.075 Ω/km (illustrative values), at 400 V.
Find: Voltage drop in volts and as a percentage.
Try it first — your answer (%): Check
1 FormulaΔV = √3 · I · L · (R cos φ + X sin φ)
2 sin φsin φ = √(1 − 0.85²) = 0.527
3 Impedance termR cos φ + X sin φ = 0.494×0.85 + 0.075×0.527 = 0.4594 Ω/km
4 Voltage dropΔV = 1.732 × 120 × 0.08 × 0.4594 = 7.64 V
5 PercentageΔV% = 7.64 ÷ 400 × 100 = 1.91 %
Answer: ΔV ≈ 7.64 V ≈ 1.91 %
Given: A plant takes 200 kW at PF 0.75. The target is PF 0.95. Supply 400 V.
Find: Capacitor kvar required and the current before and after.
Try it first — your answer (kvar): Check
1 FormulaQ_c = P · (tan φ₁ − tan φ₂)
2 Anglestan(acos 0.75) = 0.8819 tan(acos 0.95) = 0.3287
3 Required kvarQ_c = 200 × (0.8819 − 0.3287) = 110.6 kvar
4 Current before and afterI₁ = 200,000 ÷ (1.732 × 400 × 0.75) = 384.9 A I₂ = 200,000 ÷ (1.732 × 400 × 0.95) = 303.9 A
The current falls by 21 %, freeing cable and transformer capacity. Choose the next standard bank size and check harmonics before choosing a plain or detuned bank.
Answer: Q_c ≈ 110.6 kvar; current 385 A → 304 A
Given: A 55 kW, 400 V three-phase motor has efficiency 0.93 and power factor 0.86 at full load.
Find: Full-load current, and approximate starting current for DOL and star-delta.
Try it first — your answer (A): Check
1 Input powerThe rating is shaft (output) power, so divide by efficiency.
P_in = 55 ÷ 0.93 = 59.1 kW
2 Full-load currentI = P_in ÷ (√3 · V · cos φ) = 59,140 ÷ (1.732 × 400 × 0.86) = 99.3 A
3 Direct-on-line startStarting current is commonly 6–8 × FLC (check the motor data sheet):
I_start ≈ 7 × 99 ≈ 695 A
4 Star-delta startIn star the line current is about one third of the DOL value:
I_start(Y) ≈ 695 ÷ 3 ≈ 232 A
Answer: FLC ≈ 99.3 A; DOL start ≈ 695 A; star-delta ≈ 232 A
Given: Phase currents are L1 = 80 A, L2 = 45 A, L3 = 20 A, all at the same power factor, sinusoidal (no harmonics).
Find: The neutral current.
Try it first — your answer (A): Check
1 IdeaThe neutral carries the phasor sum of the three phase currents, 120° apart.
2 Formula for equal power factorsI_N = √(I₁² + I₂² + I₃² − I₁I₂ − I₂I₃ − I₃I₁)
3 SubstituteI_N = √(80² + 45² + 20² − 80×45 − 45×20 − 20×80) I_N = √(8825 − 6100) = 52.2 A
4 InterpretBalanced loads give 0 A. With non-linear loads (LED drivers, IT, VFDs) third harmonics add in the neutral and the real value can be much higher — measure with a true-RMS meter.
Answer: I_N ≈ 52.2 A
Given: A vertical rod 3 m long and 16 mm diameter is driven in uniform soil of resistivity 100 Ω·m.
Find: Approximate earth resistance.
Try it first — your answer (Ω): Check
1 Formula (Dwight)R = ρ ÷ (2πL) · [ln(8L ÷ d) − 1]
2 First termρ ÷ (2πL) = 100 ÷ (2π × 3) = 5.305 Ω
3 Log termln(8 × 3 ÷ 0.016) − 1 = ln(1,500) − 1 = 6.313
4 ResultR = 5.305 × 6.313 = 33.5 Ω
Longer rods help more than thicker rods. Several rods in parallel help only if spaced well apart. Always confirm by measurement.
Answer: R ≈ 33.5 Ω
Given: A copper XLPE cable (k = 143) must withstand 25 kA for 0.5 s.
Find: Minimum conductor cross-section.
Try it first — your answer (mm²): Check
1 Formula (adiabatic)S ≥ √(I² · t) ÷ k
2 I²tI²t = 25,000² × 0.5 = 312,500,000 A²s
3 Minimum sizeS = √312,500,000 ÷ 143 = 17,678 ÷ 143 = 123.6 mm²
4 SelectThe next standard size is 150 mm². Faster protection shrinks this a lot: at 0.1 s the minimum is 55.3 mm².
Answer: S_min ≈ 123.6 mm² → select 150 mm²
Given: An overcurrent relay uses the IEC standard inverse curve, pick-up Is = 400 A (primary) and TMS = 0.2. A fault of 4,000 A flows.
Find: Relay operating time.
Try it first — your answer (s): Check
1 Curve equation (IEC 60255 standard inverse)t = TMS × 0.14 ÷ (M^0.02 − 1)
2 Multiple of settingM = I ÷ Is = 4,000 ÷ 400 = 10.0
3 Denominator10^0.02 − 1 = 0.04713
4 Operating timet = 0.2 × 0.14 ÷ 0.04713 = 0.594 s
An upstream relay seeing the same fault must operate a grading margin later (often around 0.3–0.4 s, depending on breaker and relay type).
Answer: t ≈ 0.59 s
Given: A 20 m × 10 m workshop needs an average of 500 lux. Each luminaire gives 4,000 lm. Utilisation factor 0.6, maintenance factor 0.8.
Find: Number of luminaires.
Try it first — your answer: Check
1 FormulaN = (E × A) ÷ (F × UF × MF)
2 AreaA = 20 × 10 = 200 m²
3 SubstituteN = (500 × 200) ÷ (4,000 × 0.6 × 0.8) = 100,000 ÷ 1,920 = 52.1
4 Round to a layoutRound up to a regular grid: 53 → for example 6 rows × 9 = 54 luminaires. Verify uniformity and glare with lighting software.
Answer: N ≈ 52.1 → 54 luminaires (6 × 9 grid)
Show step 1 Show full solution
Given: A pump motor draws 15 kW from the supply and runs 18 hours a day for 30 days. Assume an energy price of 0.20 per kWh (use your own tariff).
Find: Monthly energy and cost, and the saving if a VFD cuts the input power by 25 %.
Try it first — your answer (kWh): Check
1 EnergyE = P × t = 15 × 18 × 30 = 8,100 kWh
2 CostCost = 8,100 × 0.20 = 1,620 per month
3 With a VFDE = 8,100 × 0.75 = 6,075 kWh → saving 405 per month
Real savings depend on the pump curve and system — affinity laws give large savings only where flow can actually be reduced.
Answer: 8,100 kWh ≈ 1,620 per month
Show step 1 Show full solution
Given: A cable's tabulated rating is 260 A (illustrative). It runs at a higher ambient (factor 0.91) and is grouped with other circuits (factor 0.79).
Find: The derated rating Iz, and whether a 200 A device can protect it.
Try it first — your answer (A): Check
1 FormulaIz = It × Ca × Cg × Ci
2 SubstituteIz = 260 × 0.91 × 0.79 × 1.0 = 186.9 A
3 CheckIn ≤ Iz → 200 ≤ 187? No
The 200 A device does not protect this cable. Use a larger cable, reduce grouping, or a lower setting if the load allows.
Answer: Iz ≈ 186.9 A — not enough for a 200 A device