Students · exam practice

Solved problems, step by step.

14 worked numericals — three-phase power, transformers, per-unit fault level, cables, protection, motors, earthing and lighting. Try each one first, check your answer, then open the solution one step at a time.

01

Line current of a three-phase load

Fundamentals Basic✓ solved

Given: A balanced three-phase load takes 50 kW at 400 V (line-to-line) and power factor 0.85 lagging.

Find: Line current, apparent power and reactive power.

Check with the calculator →
02

Same load connected in star and in delta

Fundamentals Intermediate✓ solved

Given: Three identical impedances of 10 Ω at 30° (inductive) are connected to a 400 V three-phase supply, first in star, then in delta.

Find: Line current and total power in each connection.

03

Transformer full-load current on both sides

Transformers Basic✓ solved

Given: A 1000 kVA, 11/0.4 kV three-phase distribution transformer.

Find: Rated current on the HV and LV sides.

Check with the calculator →
04

LV fault level using the per-unit method

Short circuit Advanced✓ solved

Given: An 11 kV source with a fault level of 250 MVA feeds a 1000 kVA, 6 % impedance, 11/0.4 kV transformer. Use a 10 MVA base. Ignore resistance and cable impedance.

Find: Three-phase fault current at the transformer LV terminals.

Check with the calculator →
05

Voltage drop on a three-phase feeder

Cables Basic✓ solved

Given: A feeder carries 120 A at PF 0.85 over 80 m of cable with R = 0.494 Ω/km and X = 0.075 Ω/km (illustrative values), at 400 V.

Find: Voltage drop in volts and as a percentage.

Check with the calculator →
06

Capacitor size for power factor correction

Power quality Intermediate✓ solved

Given: A plant takes 200 kW at PF 0.75. The target is PF 0.95. Supply 400 V.

Find: Capacitor kvar required and the current before and after.

Check with the calculator →
07

Motor full-load current and starting current

Motors Basic✓ solved

Given: A 55 kW, 400 V three-phase motor has efficiency 0.93 and power factor 0.86 at full load.

Find: Full-load current, and approximate starting current for DOL and star-delta.

Check with the calculator →
08

Neutral current with unbalanced phases

Fundamentals Intermediate✓ solved

Given: Phase currents are L1 = 80 A, L2 = 45 A, L3 = 20 A, all at the same power factor, sinusoidal (no harmonics).

Find: The neutral current.

See it animated →
09

Resistance of a single earth rod

Earthing Intermediate✓ solved

Given: A vertical rod 3 m long and 16 mm diameter is driven in uniform soil of resistivity 100 Ω·m.

Find: Approximate earth resistance.

Check with the calculator →
10

Minimum cable size for short-circuit withstand

Cables Intermediate✓ solved

Given: A copper XLPE cable (k = 143) must withstand 25 kA for 0.5 s.

Find: Minimum conductor cross-section.

Check with the calculator →
11

IDMT relay operating time

Protection Intermediate✓ solved

Given: An overcurrent relay uses the IEC standard inverse curve, pick-up Is = 400 A (primary) and TMS = 0.2. A fault of 4,000 A flows.

Find: Relay operating time.

Check with the calculator →
12

Number of luminaires — lumen method

Lighting Basic✓ solved

Given: A 20 m × 10 m workshop needs an average of 500 lux. Each luminaire gives 4,000 lm. Utilisation factor 0.6, maintenance factor 0.8.

Find: Number of luminaires.

13

Monthly energy of a pump

Energy Basic✓ solved

Given: A pump motor draws 15 kW from the supply and runs 18 hours a day for 30 days. Assume an energy price of 0.20 per kWh (use your own tariff).

Find: Monthly energy and cost, and the saving if a VFD cuts the input power by 25 %.

14

Derated current rating of a cable

Cables Basic✓ solved

Given: A cable's tabulated rating is 260 A (illustrative). It runs at a higher ambient (factor 0.91) and is grouped with other circuits (factor 0.79).

Find: The derated rating Iz, and whether a 200 A device can protect it.

Check with the calculator →