Interactive simulator
Fault & protection simulator.
Place a three-phase fault anywhere on a typical MV/LV radial system and watch the protection respond. See the prospective fault current, which device trips first, the grading margin — and what happens when settings are wrong.
Educational model. Three-phase symmetrical faults on a radial system; impedances added as complex values (source as pure reactance, transformer with the X/R you enter, cables with the R and X you enter). Devices use IEC 60255-151 inverse curves plus an optional definite-time high-set stage — LV breaker trip units are approximated by these curves. Not a protection coordination study.
⚡ = fault location (click or press Enter). Green lines are energised, red show fault current, grey dashed are disconnected after the trip.
Result
Click a ⚡ marker on the diagram to apply a three-phase fault.
Protection settings
R1 settings are in MV amperes; all others in LV amperes. Change any value and the last fault re-runs.
Network data
How to use the simulator
- Pick a fault location.Click a ⚡ marker: MV cable, LV busbar or the end of any feeder.
- Read the fault current.The prospective three-phase fault current is calculated from source, transformer and cable impedance.
- Watch the trip.Every device between source and fault times out on its curve; the fastest one trips and the network downstream of it is disconnected.
- Judge selectivity.The verdict states whether the nearest device cleared the fault and whether the margin to the next device meets your target.
- Break it on purpose.Load a mis-coordinated preset or change TMS and high-set values to see how selectivity is lost.
What the presets teach
Well coordinated
Feeder MCCBs clear feeder faults almost instantly; the incomer and MV relay are graded behind them. A busbar fault is cleared by the incomer with margin to the MV relay.
Incomer set too fast
A low incomer TMS and high-set stage race the feeder breaker. A fault on Feeder 1 trips the whole LV board — classic loss of selectivity.
MV high-set too low
The MV relay's instantaneous stage sees an LV busbar fault (referred to MV) and trips the transformer feeder before the LV incomer can act.
Model limits
- Only balanced three-phase faults; earth faults, phase-to-phase faults and arcing faults behave differently.
- No motor contribution, no DC offset, no CT saturation, no breaker opening times or relay tolerances.
- LV breaker trip units are approximated with IEC inverse curves and a definite-time stage; real devices have their own published bands.
- Use proper protection studies, manufacturer data and approved settings for real equipment.