Interactive simulator

Fault & protection simulator.

Place a three-phase fault anywhere on a typical MV/LV radial system and watch the protection respond. See the prospective fault current, which device trips first, the grading margin — and what happens when settings are wrong.

Educational model. Three-phase symmetrical faults on a radial system; impedances added as complex values (source as pure reactance, transformer with the X/R you enter, cables with the R and X you enter). Devices use IEC 60255-151 inverse curves plus an optional definite-time high-set stage — LV breaker trip units are approximated by these curves. Not a protection coordination study.

System healthy — select a fault locationWell coordinated

⚡ = fault location (click or press Enter). Green lines are energised, red show fault current, grey dashed are disconnected after the trip.

Result

Click a ⚡ marker on the diagram to apply a three-phase fault.

Protection settings

R1 settings are in MV amperes; all others in LV amperes. Change any value and the last fault re-runs.

Network data

How to use the simulator

  1. Pick a fault location.Click a ⚡ marker: MV cable, LV busbar or the end of any feeder.
  2. Read the fault current.The prospective three-phase fault current is calculated from source, transformer and cable impedance.
  3. Watch the trip.Every device between source and fault times out on its curve; the fastest one trips and the network downstream of it is disconnected.
  4. Judge selectivity.The verdict states whether the nearest device cleared the fault and whether the margin to the next device meets your target.
  5. Break it on purpose.Load a mis-coordinated preset or change TMS and high-set values to see how selectivity is lost.

What the presets teach

Preset 1

Well coordinated

Feeder MCCBs clear feeder faults almost instantly; the incomer and MV relay are graded behind them. A busbar fault is cleared by the incomer with margin to the MV relay.

Preset 2

Incomer set too fast

A low incomer TMS and high-set stage race the feeder breaker. A fault on Feeder 1 trips the whole LV board — classic loss of selectivity.

Preset 3

MV high-set too low

The MV relay's instantaneous stage sees an LV busbar fault (referred to MV) and trips the transformer feeder before the LV incomer can act.

Model limits

  • Only balanced three-phase faults; earth faults, phase-to-phase faults and arcing faults behave differently.
  • No motor contribution, no DC offset, no CT saturation, no breaker opening times or relay tolerances.
  • LV breaker trip units are approximated with IEC inverse curves and a definite-time stage; real devices have their own published bands.
  • Use proper protection studies, manufacturer data and approved settings for real equipment.