What happenedLV voltage was about 5 % high after energisation; several sensitive loads alarmed.
Root causeTap position not checked against the design setting; commissioning checklist had no tap item.
How to prevent itAdd tap position (and the expected LV voltage) to the pre-energisation checklist; record it with a photo.
What happenedA new MV cable failed at a joint in the first month.
Root causeJoint made in the open during dusty, humid conditions; the kit's cleanliness instructions were not followed; no shelter.
How to prevent itJoint only in a clean, covered enclosure; jointer competence record; check kit expiry and instructions at the ITP hold point.
What happenedTwo pumps ran in reverse during the first test; one impeller was damaged.
Root causePhase rotation not checked after the supply cable was re-terminated; motors were bump-tested coupled.
How to prevent itCheck phase rotation at the MCC and bump-test uncoupled after any re-termination.
What happenedDuring a short-circuit study review, a final DB's MCB was found to have a breaking capacity below the prospective fault current.
Root causeDB moved closer to the transformer during design changes; fault level not recalculated.
How to prevent itRecalculate fault levels after any layout change; include Icu checks in the design change checklist.
What happenedUpstream breaker tripped every time a transformer was energised.
Root causeInstantaneous setting below the transformer's magnetising inrush current.
How to prevent itCheck inrush against instantaneous settings during coordination studies; review settings before energisation.
What happenedMany nuisance trips on an LED lighting circuit.
Root causeToo many LED drivers on one RCD — cumulative earth leakage and switching inrush.
How to prevent itLimit drivers per RCD per manufacturer data; split circuits; use suitable RCD types.
What happenedFinal circuits installed in 2.5 mm² where the revision required 4 mm².
Root causeSuperseded drawing left in the site office; the crew used it.
How to prevent itDrawing register checks, stamp and remove superseded prints, issue revision notices at toolbox talks.
What happenedHandover earth resistance passed; summer readings were more than double.
Root causeMeasured during wet season; dry sandy soil; electrode too short.
How to prevent itDesign for dry-season resistivity; deeper electrodes or enhancement as designed; record conditions with readings.
What happenedMotor bearings failed early; VFD gave repeated earth-fault trips.
Root causeUnscreened motor cable, screens not terminated 360°, long cable run beyond drive guidance.
How to prevent itUse the drive manufacturer's cable and gland requirements; output filters for long runs; check bearing-current mitigation.
What happenedInsulation readings were identical on every circuit and floor.
Root causeResults copied rather than measured; test instrument calibration had expired.
How to prevent itWitness sample tests; check instrument serial numbers and calibration on every sheet; random re-tests.
What happenedRainwater flowed through ducts into the RMU base and caused tracking.
Root causeDuct ends not sealed after cable installation; no fall away from the substation.
How to prevent itSeal ducts immediately; inspect duct sealing as an ITP item; coordinate drainage with civil.
What happenedThe neutral conductor and terminal were discoloured though phases were within rating.
Root causeMany single-phase non-linear loads; third-harmonic currents added in the neutral.
How to prevent itMeasure with true-RMS meters; size neutrals for harmonic loading; balance phases; consider filtering.