Department 11 / 12

PLC, SCADA & Industrial Automation

Control-system architecture, PLC hardware and scan cycle, I/O and 4–20 mA loops, communication protocols, HMI and alarms, FAT/SAT and OT security.

3 diagrams1 interactive tools10 checklist items1 related guides
Illustration: PLC, SCADA & Industrial Automation
Original illustration

Automation connects the electrical system to the process it serves. PLCs make the decisions, instruments and actuators connect them to the physical world, and SCADA gives people visibility and control. For electrical engineers the interfaces — signals, power, earthing, communications and security — are where projects succeed or fail.

What this department covers

  • Automation architecture and network segmentation
  • PLC hardware and the scan cycle
  • Digital and analogue I/O, 4–20 mA loops
  • Communication protocols
  • HMI, alarms and historians
  • FAT, SAT and loop checks
  • OT cybersecurity basics
Field → Control → Supervisorylayered architecture
IEC 61131-3PLC programming languages
4–20 mAlive-zero analogue standard
IEC 62443industrial cybersecurity series

01Architecture and segmentation

Industrial control systems are organised in layers: field devices at the process, controllers (PLCs, RTUs, protection IEDs, drives) that execute logic, supervisory systems (SCADA servers, HMIs, historians, engineering workstations) that present information and accept operator commands, and enterprise systems that use the data. Good architectures separate these layers into network zones connected through controlled conduits — firewalls and a demilitarised zone (DMZ) between the control network and the business network.

Layered automation architecture with a DMZ between business and control networks
Figure 1.Layered automation architecture with a DMZ between business and control networks. Zone design, redundancy and protocols are project decisions.
SCADA, DCS and PLC — typical roles
SystemTypical useCharacteristics
PLCMachine and process control (pump stations, MCC logic, packaging, HVAC plant)Deterministic cyclic execution; robust I/O
RTURemote outstations on wide-area networksTelemetry protocols, low power, time-stamped events
DCSContinuous process plant (power, oil & gas, chemicals)Integrated control, engineering and HMI environment
SCADASupervisory control over distributed assets (water networks, electrical networks)Data acquisition, alarms, trends, remote control
Substation automation (IEDs)Protection and control of electrical substationsOften IEC 61850-based, time-synchronised

02PLC hardware and the scan cycle

A PLC consists of a power supply, CPU, I/O modules (digital, analogue, special function), communication modules and a rack or backplane — or a compact all-in-one unit. It runs its program cyclically: read inputs into a process image, execute the logic, write outputs, then handle communications and diagnostics. The cycle time affects how quickly the PLC responds; a watchdog stops outputs safely if the cycle overruns.

The PLC scan cycle
Figure 2.The PLC scan cycle. Program languages per IEC 61131-3 include ladder diagram, function block diagram, structured text and sequential function chart.
Electrical design points for PLC panels
ItemGood practice
Power suppliesSeparate supplies for logic and field I/O where appropriate; UPS for continuity; supply monitoring
SegregationSeparate power and signal wiring; analogue signals away from VFD and motor cables
EarthingDedicated clean/instrument earth arrangement per manufacturer and design; screens earthed at one end unless design says otherwise
HeatPanel heat-load calculation; ventilation or cooling for drives and power supplies
Spare capacitySpare I/O and panel space as specified
LabellingWire and terminal numbering matching the I/O list and loop drawings

03Signals and I/O

Digital inputs carry states (running, tripped, open/closed, level switches); digital outputs drive contactors, solenoids and indicators — usually through interposing relays. Analogue signals carry continuous values; the most common is the 4–20 mA current loop, where 4 mA represents the bottom of the range and 20 mA the top. Using 4 mA rather than 0 mA as the "zero" means a broken wire (0 mA) can be distinguished from a genuine minimum reading.

Two-wire 4–20 mA loop and linear scaling to engineering units
Figure 3.Two-wire 4–20 mA loop and linear scaling to engineering units.
Value = LRV + (I − 4 mA) / 16 mA × (URV − LRV)
R_loop,max = (U_supply − U_transmitter,min) / 0.020 AMany projects adopt the NAMUR NE 43 convention, which treats signals at or below 3.6 mA or at or above 21 mA as device failure. Confirm the convention used by your transmitters and PLC cards.

04Communication protocols

Common industrial protocols (selection depends on equipment and project standards)
ProtocolTypical useNotes
Modbus RTU / TCPSimple data exchange with meters, drives, packaged equipmentWidely supported; limited native security
PROFIBUS / PROFINETField devices and drives in many process and factory plantsDeterministic options; vendor ecosystems
EtherNet/IPIndustrial Ethernet in many automation systemsCommon in some vendor ecosystems
DNP3Utility SCADA telemetry, RTUsTime-stamped events; secure authentication variants
IEC 60870-5-101/104Telecontrol for electrical networksCommon in utility control centres
IEC 61850Substation automation, protection IEDsGOOSE messaging, sampled values, structured data models
OPC UAPlatform-independent data exchange to SCADA/MES/ITBuilt-in security model
HARTDigital data superimposed on 4–20 mADevice diagnostics and configuration

05HMI, alarms and historians

An HMI should help operators understand and act, not merely display data. Effective displays show the process in a clear hierarchy, use colour sparingly (reserving strong colours for abnormal states), and present alarms that are meaningful, prioritised and actionable. Alarm management practice — such as that described in alarm-management standards used in industry — aims to avoid alarm floods by rationalising each alarm's purpose, priority and response. Historians store time-series data for trending, reporting and investigation; time synchronisation across devices is essential for event analysis.

06FAT, SAT and loop checks

  1. Factory acceptance test (FAT).Panel inspection, power-up, I/O simulated against the I/O list, logic tested against the functional design specification, HMI screens and alarms reviewed.
  2. Installation checks.Panel installation, cable glanding, segregation, earthing and screen terminations.
  3. Loop checks.Every signal proven from field device to PLC to HMI/SCADA, with analogue values injected at several points across the range.
  4. Site acceptance test (SAT).Integrated functional testing with real equipment: sequences, interlocks, trips, failure modes and communications loss.
  5. Performance and handover.Tuning (e.g. PID loops), operator training, backups of final programs and configurations, and documentation.

07OT cybersecurity basics

Control systems are increasingly connected, so security is an engineering requirement. The IEC 62443 series provides a widely used framework based on zones and conduits, security levels and secure development and maintenance practices. Practical baseline measures include network segmentation, removing default passwords, disabling unused services and ports, controlled remote access through a jump host, managed backups of PLC programs and configurations, and change control for any modification.

Never connect a laptop or modem to a live control network without authorisation and a change-control record. Uncontrolled remote access is one of the most common weaknesses found in industrial systems.

08Troubleshooting

Automation troubleshooting
SymptomLikely causesChecks
Analogue value frozen or at limitOpen circuit, fuse/blown loop supply, transmitter faultMeasure loop current; check supply and terminals; compare with NE 43 thresholds
Noisy analogue readingScreen not earthed or earthed both ends, routing near VFD cablesCheck screen termination and segregation; filtering
Intermittent communication lossTermination resistors, cable damage, duplicate IP/node addresses, network loopsDiagnostics counters; address list; topology review
HMI value differs from fieldScaling mismatch between transmitter, PLC and SCADAAlign LRV/URV in all three; inject known signal
PLC stops / faultsWatchdog cycle overrun, module failure, power dipDiagnostic buffer; supply quality; program changes

Automation loop check & SAT readiness

0 / 10
  • Documentation
  • Installation
  • Loop checks
  • SAT
Ticks are saved only in this browser. Adapt the list to the approved ITP and manufacturer instructions; it does not define acceptance criteria.

09Test yourself

Ten questions with explanations. Scores are saved only in your browser and feed your learning progress dashboard.