RMUs & Switchgear

Ring main units, MV switchgear and LV assemblies — functions, interlocks, ratings, operation, inspection and maintenance.

4 diagrams0 interactive tools12 checklist items3 related guides
Illustration: RMUs & Switchgear
Original illustration

Switchgear is where electrical energy is controlled, protected and isolated. RMUs, MV switchboards and LV assemblies each combine switching devices, interlocks and indications — and every one of them must be understood before it is operated, inspected or maintained.

What this department covers

  • RMU functions and configurations
  • Switching devices and their duties
  • Interlocks and safe isolation
  • MV switchgear ratings
  • LV assemblies and forms of separation
  • Inspection and maintenance
  • Troubleshooting
LBS · CB · ESload-break switch, circuit breaker, earth switch
RRTtwo ring ways + one transformer way
Interlocksprevent unsafe operating sequences
Icw · Ip · IACshort-time, peak and internal-arc ratings

01What a ring main unit does

A ring main unit is compact, factory-assembled MV switchgear used at secondary substations on open-ring networks. A common configuration has two ring ways fitted with load-break switches and earth switches, and one tee-off way that protects the transformer with either a fuse-switch combination or a circuit breaker controlled by a protection relay. Insulation may be gas (commonly SF₆, with alternatives increasingly available), solid or air, depending on design.

Typical 'RRT' RMU: two ring switches with earth switches and voltage presence indicators, and a transformer protection way
Figure 1.Typical 'RRT' RMU: two ring switches with earth switches and voltage presence indicators, and a transformer protection way.
Switching devices and their capabilities
DeviceCan make load currentCan break load currentCan break fault currentTypical use
Disconnector (isolator)No (off-load)NoNoProvide isolation distance
Load-break switch (LBS)YesYesNoRMU ring ways, feeder switching
Fuse-switch combinationYesYesFuses clear faultsTransformer protection on smaller ratings
Circuit breaker (CB)YesYesYesFeeders, transformers, incomers with relays
Earth switch (ES)Fault-making rated types can close onto a live circuit safely——Earthing a de-energised circuit for work

Ratings that matter for MV switchgear include rated voltage, rated normal current, short-time withstand current and duration (Icw, t), peak withstand current, breaking and making capacities, and — where specified — internal arc classification (IAC), which describes the protection provided to persons near the switchgear if an internal arc occurs.

02Reading the front panel

Generic RMU front: mimic, position indicators, operating sockets, padlock facilities, VPIS, gas pressure gauge, relay and FPI
Figure 2.Generic RMU front: mimic, position indicators, operating sockets, padlock facilities, VPIS, gas pressure gauge, relay and FPI.

Each element of the front panel communicates state or enforces safety. Position indicators show switch and earth-switch status (but are not the same as proof of isolation). Voltage presence indicating systems (VPIS) show that voltage is present — they are an indication, not a proving device. Gas pressure gauges show whether the insulating medium is within the manufacturer's operating zone. Fault passage indicators show whether fault current passed through the way, helping operators locate faulted cable sections.

03Interlocks and safe operation

Interlocks prevent operating sequences that would endanger people or equipment. Typical examples are that an earth switch cannot be closed while the associated main switch is closed, that the cable compartment cover cannot be removed unless the way is earthed, and that fuse access is only possible when the fuse-switch is open and both sides are earthed. The exact logic is specific to the product and is documented in the manufacturer's manual.

The control sequence for safe isolation — always under the applicable safety rules and permit-to-work system
Figure 3.The control sequence for safe isolation — always under the applicable safety rules and permit-to-work system.

Never defeat or bypass an interlock, and never operate switchgear you are not authorised and competent to operate. Voltage indicators and mimic positions are not proof of dead — only an approved test performed in accordance with the safety rules is.

04MV switchboards

Larger installations use metal-enclosed MV switchboards with withdrawable or fixed circuit breakers, busbars, CTs and VTs, protection relays and control wiring. They add functional choices that RMUs simplify away: bus sections and couplers, incomer interlocking, auto-changeover schemes, and comprehensive protection and metering. Commissioning therefore extends to secondary wiring checks, CT/VT tests, relay injection, scheme tests (intertrips, interlocks, auto-transfer) and SCADA point-to-point testing.

MV switchboard review points
AreaWhat to confirm
RatingsVoltage, normal current, Icw/t, peak, breaking capacity ≥ study values
Busbar arrangementSingle bus, sectionalised, coupler — matches SLD and operating philosophy
CTs and VTsRatios, classes, burdens and locations per protection/metering design
InterlockingMechanical and electrical interlocks per logic diagrams; key interlocks with transformers or LV boards
Control supplyDC battery/charger capacity and supervision; trip circuit supervision
Internal arcClassification and pressure-relief routing if specified
OperationOperating sequences documented; operator training planned

05LV switchboards and assemblies

LV switchboards (main distribution boards, MCCs, distribution boards) are assemblies whose ratings depend on the design as a whole — busbars, enclosures, devices and their arrangement — not only on the devices fitted. Design verification by the assembly manufacturer, under the applicable assembly standard (IEC 61439 series in many markets), provides evidence for temperature rise, short-circuit withstand, dielectric properties and other characteristics.

Generic LV main switchboard front elevation
Figure 4.Generic LV main switchboard front elevation.

Forms of separation describe how the assembly is divided internally — separating busbars from functional units, and functional units from each other and from their terminals — to allow work on one part while others remain live, where safety rules permit. The form required is a specification decision; it should match the client's operational and maintenance philosophy.

06Inspection and maintenance

Typical inspection and maintenance activities (scope and intervals per manufacturer and asset owner)
ActivityPurposeNotes
Visual inspectionDamage, corrosion, contamination, labelsIncludes cable boxes and glands
Gas pressure check (gas-insulated)Insulation integrityCompare with manufacturer's zone; follow manufacturer instructions for low pressure
Mechanical operationMechanisms operate freely; indicators correctOnly under authorised switching arrangements
Interlock verificationInterlocks prevent prohibited operationsPer manufacturer test procedure
Thermography (energised, under load)Hot joints and connectionsFrom safe positions, through approved windows where provided
Relay and trip circuit testsProtection operatesSecondary injection; trip circuit supervision healthy
Partial discharge surveys (where adopted)Early insulation degradationTrend over time

07Troubleshooting

Switchgear troubleshooting
SymptomLikely causesFirst actions
Low gas pressure indicationLeak, temperature effect, gauge faultFollow manufacturer instructions; restrict operation as instructed; notify asset owner
Switch will not operateInterlock engaged, mechanism fault, incorrect handle/sequenceCheck interlock conditions and sequence in the manual; do not force
CB trips immediately on closingFault on circuit, earth switch closed downstream, relay settings, trip circuit wiringCheck circuit state and event records; test before re-closing under authorised procedure
FPI showing fault on a healthy-looking wayFault downstream, FPI not reset, sensitivity settingRead FPIs along the ring to locate section; reset per instructions
Hot spot on thermographyLoose or under-torqued connection, undersized linkPlan outage; inspect, clean and re-torque per manufacturer

RMU / switchgear pre-energisation inspection

0 / 12
  • Documentation
  • Physical
  • Functional
  • Release
Ticks are saved only in this browser. Adapt the list to the approved ITP and manufacturer instructions; it does not define acceptance criteria.