Earthing & Bonding

System earthing arrangements, protective conductors, main bonding, electrodes and grids, soil resistivity, touch and step voltage, and earth testing.

5 diagrams1 interactive tools10 checklist items2 related guides
Illustration: Earthing & Bonding
Original illustration

Earthing and bonding are what make faults survivable. They give fault current a defined path so protection can operate, limit the voltages people can touch, and keep metalwork at the same potential. They are also among the most frequently misunderstood topics on site.

What this department covers

  • Earthing vs bonding
  • LV system earthing arrangements (TN-S, TN-C-S, TT)
  • Protective conductors and main bonding
  • Electrodes, grids and soil resistivity
  • Touch and step voltage
  • Earth testing
  • Inspection and troubleshooting
Earthingconnection to the general mass of earth
Bondingequalising potential between metal parts
TN · TTsystem arrangements set by the supply
Touch & stepthe voltages that injure people

01Earthing versus bonding

Earthing connects parts of the installation to the general mass of earth — through electrodes, grids and the supply's earth path — so that fault current has a defined route back to the source and protective devices can operate. Protective equipotential bonding connects exposed and extraneous conductive parts together so that, during a fault, simultaneously accessible parts rise to similar potentials and the voltage between them stays low. Both are needed; neither replaces the other.

The main earthing terminal links the earthing conductor, circuit protective conductors and main protective bonding to services and structura
Figure 1.The main earthing terminal links the earthing conductor, circuit protective conductors and main protective bonding to services and structural metalwork.
Exposed-conductive-part
Metalwork of equipment that is not normally live but can become live under a fault (e.g. a motor frame).
Extraneous-conductive-part
Metalwork not part of the installation that can introduce a potential, often earth potential (e.g. metallic water pipes, structural steel).
Circuit protective conductor (CPC)
Conductor connecting exposed-conductive-parts to the main earthing terminal.
Main earthing terminal (MET)
The terminal or bar where protective, bonding and earthing conductors meet.
Earth electrode
Conductive part in contact with the ground — rods, tapes, plates, foundation earth electrodes or a grid.
Earth potential rise (EPR/GPR)
Rise in potential of the earthing system relative to remote earth during an earth fault.
Animated: the earth-fault loop in a TN-S system — line conductor, fault, enclosure, protective conductor, MET and back to the star point — u
Figure 2.Animated: the earth-fault loop in a TN-S system — line conductor, fault, enclosure, protective conductor, MET and back to the star point — until the device disconnects.

02LV system earthing arrangements

The system earthing arrangement describes how the supply source and the installation's exposed-conductive-parts are related to earth. The first letter describes the source (T: directly earthed; I: isolated or impedance-earthed); the second describes the installation's exposed parts (T: own earth electrode; N: connected to the source neutral/earth). In TN systems the suffix shows whether neutral and protective functions are separate (S), combined (C) or combined then separated (C-S).

TN-S, TN-C-S and TT arrangements
Figure 3.TN-S, TN-C-S and TT arrangements. Which is used — and any additional local electrode or RCD requirement — is set by the utility and applicable regulations.
Comparing common arrangements
ArrangementFault return pathTypical protective measurePoints to watch
TN-SSeparate PE conductor back to sourceOvercurrent devices (low loop impedance), RCDs where requiredPE continuity; N and PE never re-joined downstream
TN-C-S (PME/PNB variants)Combined PEN in supply, separate N and PE in installationOvercurrent devices; bonding is especially importantConsequences of a broken PEN; utility rules on use and extra electrodes
TTThrough installation electrode and earth back to source electrodeRCDs (loop impedance usually too high for overcurrent disconnection)Electrode resistance stability; RCD coordination
ITSource isolated or high-impedance earthedInsulation monitoring; second-fault disconnectionUsed for continuity of supply in special applications

03Protective conductors and bonding

Protective conductors must be continuous, correctly identified (green-and-yellow in many regions), adequately sized for the fault current and duration they may carry, and mechanically protected. Their size can be selected from tables in the applicable wiring regulations or calculated with the adiabatic equation using the protective device's let-through energy. Main protective bonding conductors connect incoming metallic services and structural metalwork to the MET; supplementary bonding is used in specific locations where the regulations or the design require it.

The neutral–earth link must exist only where the design places it (typically at the source or origin of the installation). An additional N–E connection downstream creates parallel current paths, defeats RCDs and causes nuisance earth-fault trips.

04Electrodes, grids and soil resistivity

An earth electrode's resistance depends mostly on soil resistivity — which varies greatly with soil type, moisture, temperature and depth — and on electrode geometry. Driving a rod deeper into lower-resistivity layers often achieves more than adding short rods close together, because closely spaced rods share the same volume of soil (mutual resistance). Substation earthing uses buried grids with rods to control potential gradients as well as resistance.

Substation earth grid plan: mesh conductor, rods and test points, and connections to equipment
Figure 4.Substation earth grid plan: mesh conductor, rods and test points, and connections to equipment. Sizing and layout come from the earthing study.
R ≈ ρ / (2π·L) · [ ln(8L/d) − 1 ]Single vertical rod of length L and diameter d in uniform soil of resistivity ρ (Dwight). Real soils are rarely uniform — use measured resistivity and proper design methods for anything beyond a screening estimate.
Earthing design inputs for substations
InputSourceWhy it matters
Soil resistivity profileSite survey (e.g. Wenner method) at several spacings and directionsDetermines grid resistance and layer effects
Earth fault current and durationUtility data / protection studySets GPR, touch/step voltages and conductor sizing
Current splitNetwork analysis (cable screens, overhead earth wires)Only part of fault current may flow into the grid
Surface layerDesign (e.g. crushed rock)Increases contact resistance, improving tolerable limits
Tolerable touch/step criteriaApplicable standard method (e.g. IEEE 80 or national equivalent)Defines what the design must achieve

05Touch and step voltage

During an earth fault, current flowing into the ground raises the potential of the earthing system and creates potential gradients across the surface. A person touching earthed metalwork while standing on the ground experiences a touch voltage; a person walking across the gradient experiences a step voltage. Substation earthing design aims to keep these below tolerable limits determined by recognised methods, considering fault duration and surface layer — not merely to achieve a low resistance figure.

There is no universal "good" earth resistance value. Targets come from the design: protective device operation, touch/step safety, utility requirements and equipment needs. Quote the design value — not a rule of thumb — in ITPs and test sheets.

06Earth testing

Fall-of-potential method: current probe far away, potential probe moved between electrode and current probe; the flat part of the curve give
Figure 5.Fall-of-potential method: current probe far away, potential probe moved between electrode and current probe; the flat part of the curve gives the resistance.
Common earthing tests
TestPurposeNotes
Soil resistivity (Wenner)Design inputMultiple spacings and traverses; record weather and moisture
Electrode resistance (fall-of-potential)Verify electrode against designElectrode disconnected under safe procedure; probe spacing adequate for electrode size
Clamp-on (stakeless) methodQuick check in multi-earthed systemsRequires a parallel return path; not valid on a single isolated electrode
Continuity of protective/bonding conductorsIntegrity of connectionsLow-resistance ohmmeter; include all bonds
Earth-fault loop impedanceProtective device will disconnect in timeCompare with maximum values for the device and disconnection time
RCD operationTrip time and currentPer applicable regulations

07Troubleshooting

Earthing & bonding troubleshooting
SymptomLikely causesChecks
RCD nuisance trippingAccumulated leakage, N–E fault downstream, moistureInsulation test circuits; verify N and PE separation; split circuits across RCDs
High electrode resistanceDry/rocky soil, insufficient depth, corroded connectionRe-test with proper probe spacing; inspect connection in pit; deeper rods per design
Tingle from metalworkMissing bonding, broken CPC, PEN problemContinuity test bonding; check main bonding to services; involve utility if supply side suspected
Current measured on earth conductor in normal serviceDownstream N–E connection, unbalanced loads via parallel pathsLocate and remove unintended N–E links
Corrosion at connectionsDissimilar metals, moistureUse compatible materials and protected joints per specification

Earthing & bonding inspection

0 / 10
  • Design & documents
  • Installation
  • Testing
Ticks are saved only in this browser. Adapt the list to the approved ITP and manufacturer instructions; it does not define acceptance criteria.

08Test yourself

Ten questions with explanations. Scores are saved only in your browser and feed your learning progress dashboard.