Earthing and bonding are what make faults survivable. They give fault current a defined path so protection can operate, limit the voltages people can touch, and keep metalwork at the same potential. They are also among the most frequently misunderstood topics on site.
What this department covers
- Earthing vs bonding
- LV system earthing arrangements (TN-S, TN-C-S, TT)
- Protective conductors and main bonding
- Electrodes, grids and soil resistivity
- Touch and step voltage
- Earth testing
- Inspection and troubleshooting
01Earthing versus bonding
Earthing connects parts of the installation to the general mass of earth — through electrodes, grids and the supply's earth path — so that fault current has a defined route back to the source and protective devices can operate. Protective equipotential bonding connects exposed and extraneous conductive parts together so that, during a fault, simultaneously accessible parts rise to similar potentials and the voltage between them stays low. Both are needed; neither replaces the other.
- Exposed-conductive-part
- Metalwork of equipment that is not normally live but can become live under a fault (e.g. a motor frame).
- Extraneous-conductive-part
- Metalwork not part of the installation that can introduce a potential, often earth potential (e.g. metallic water pipes, structural steel).
- Circuit protective conductor (CPC)
- Conductor connecting exposed-conductive-parts to the main earthing terminal.
- Main earthing terminal (MET)
- The terminal or bar where protective, bonding and earthing conductors meet.
- Earth electrode
- Conductive part in contact with the ground — rods, tapes, plates, foundation earth electrodes or a grid.
- Earth potential rise (EPR/GPR)
- Rise in potential of the earthing system relative to remote earth during an earth fault.
02LV system earthing arrangements
The system earthing arrangement describes how the supply source and the installation's exposed-conductive-parts are related to earth. The first letter describes the source (T: directly earthed; I: isolated or impedance-earthed); the second describes the installation's exposed parts (T: own earth electrode; N: connected to the source neutral/earth). In TN systems the suffix shows whether neutral and protective functions are separate (S), combined (C) or combined then separated (C-S).
| Arrangement | Fault return path | Typical protective measure | Points to watch |
|---|---|---|---|
| TN-S | Separate PE conductor back to source | Overcurrent devices (low loop impedance), RCDs where required | PE continuity; N and PE never re-joined downstream |
| TN-C-S (PME/PNB variants) | Combined PEN in supply, separate N and PE in installation | Overcurrent devices; bonding is especially important | Consequences of a broken PEN; utility rules on use and extra electrodes |
| TT | Through installation electrode and earth back to source electrode | RCDs (loop impedance usually too high for overcurrent disconnection) | Electrode resistance stability; RCD coordination |
| IT | Source isolated or high-impedance earthed | Insulation monitoring; second-fault disconnection | Used for continuity of supply in special applications |
03Protective conductors and bonding
Protective conductors must be continuous, correctly identified (green-and-yellow in many regions), adequately sized for the fault current and duration they may carry, and mechanically protected. Their size can be selected from tables in the applicable wiring regulations or calculated with the adiabatic equation using the protective device's let-through energy. Main protective bonding conductors connect incoming metallic services and structural metalwork to the MET; supplementary bonding is used in specific locations where the regulations or the design require it.
The neutral–earth link must exist only where the design places it (typically at the source or origin of the installation). An additional N–E connection downstream creates parallel current paths, defeats RCDs and causes nuisance earth-fault trips.
04Electrodes, grids and soil resistivity
An earth electrode's resistance depends mostly on soil resistivity — which varies greatly with soil type, moisture, temperature and depth — and on electrode geometry. Driving a rod deeper into lower-resistivity layers often achieves more than adding short rods close together, because closely spaced rods share the same volume of soil (mutual resistance). Substation earthing uses buried grids with rods to control potential gradients as well as resistance.
| Input | Source | Why it matters |
|---|---|---|
| Soil resistivity profile | Site survey (e.g. Wenner method) at several spacings and directions | Determines grid resistance and layer effects |
| Earth fault current and duration | Utility data / protection study | Sets GPR, touch/step voltages and conductor sizing |
| Current split | Network analysis (cable screens, overhead earth wires) | Only part of fault current may flow into the grid |
| Surface layer | Design (e.g. crushed rock) | Increases contact resistance, improving tolerable limits |
| Tolerable touch/step criteria | Applicable standard method (e.g. IEEE 80 or national equivalent) | Defines what the design must achieve |
05Touch and step voltage
During an earth fault, current flowing into the ground raises the potential of the earthing system and creates potential gradients across the surface. A person touching earthed metalwork while standing on the ground experiences a touch voltage; a person walking across the gradient experiences a step voltage. Substation earthing design aims to keep these below tolerable limits determined by recognised methods, considering fault duration and surface layer — not merely to achieve a low resistance figure.
There is no universal "good" earth resistance value. Targets come from the design: protective device operation, touch/step safety, utility requirements and equipment needs. Quote the design value — not a rule of thumb — in ITPs and test sheets.
06Earth testing
| Test | Purpose | Notes |
|---|---|---|
| Soil resistivity (Wenner) | Design input | Multiple spacings and traverses; record weather and moisture |
| Electrode resistance (fall-of-potential) | Verify electrode against design | Electrode disconnected under safe procedure; probe spacing adequate for electrode size |
| Clamp-on (stakeless) method | Quick check in multi-earthed systems | Requires a parallel return path; not valid on a single isolated electrode |
| Continuity of protective/bonding conductors | Integrity of connections | Low-resistance ohmmeter; include all bonds |
| Earth-fault loop impedance | Protective device will disconnect in time | Compare with maximum values for the device and disconnection time |
| RCD operation | Trip time and current | Per applicable regulations |
07Troubleshooting
| Symptom | Likely causes | Checks |
|---|---|---|
| RCD nuisance tripping | Accumulated leakage, N–E fault downstream, moisture | Insulation test circuits; verify N and PE separation; split circuits across RCDs |
| High electrode resistance | Dry/rocky soil, insufficient depth, corroded connection | Re-test with proper probe spacing; inspect connection in pit; deeper rods per design |
| Tingle from metalwork | Missing bonding, broken CPC, PEN problem | Continuity test bonding; check main bonding to services; involve utility if supply side suspected |
| Current measured on earth conductor in normal service | Downstream N–E connection, unbalanced loads via parallel paths | Locate and remove unintended N–E links |
| Corrosion at connections | Dissimilar metals, moisture | Use compatible materials and protected joints per specification |
Earthing & bonding inspection
0 / 10- Design & documents
- Installation
- Testing