Cable voltage drop: limits, formula and worked example

Voltage drop formula for single- and three-phase cables, typical 3% and 5% limits, which resistance to use (PVC 70 °C, XLPE 90 °C) and a 4 mm² vs 6 mm² worked example.

7 min readUpdated 21 Nov 2026Department: Cables & Jointing
Cables & Jointing

Voltage drop is the reduction in voltage between the source and the load caused by the impedance of the conductors. On long cable runs it often decides the cable size — a cable that carries the current comfortably can still fail the voltage drop check. Excessive voltage drop affects equipment operation, motor starting and lighting performance.

Voltage drop accumulates along every series element from the source to the final circuit.
Figure.Voltage drop accumulates along every series element from the source to the final circuit.

01Information required

  • System type: single-phase or three-phase.
  • Load current and nominal system voltage.
  • One-way route length and conductor material (copper or aluminium).
  • Conductor resistance and reactance at the operating temperature (depends on PVC or XLPE insulation).
  • Power factor for AC circuits.

02Voltage drop formula

Three-phase (balanced): ΔV = √3 × I × L × (R cosφ + X sinφ)
Single-phase (two-wire): ΔV = 2 × I × L × (R cosφ + X sinφ)
Percentage: ΔV% = ΔV ÷ V × 100

L is the one-way length in kilometres, R and X are in Ω/km. Single-phase uses a factor of 2 because current goes out on the line conductor and comes back on the neutral. If length is entered in metres, divide by 1000.

03Typical voltage drop limits (3% and 5%)

IEC 60364-5-52, Annex G, gives commonly quoted maximum values between the origin of the installation and the equipment:

Installation supplied fromLightingOther uses
Public low-voltage network (Type A)3%5%
Private LV supply / own transformer (Type B)6%8%

Many project specifications and utilities set their own (often stricter) limits per feeder and final circuit. The project specification always governs.

04Which resistance value to use

  • Temperature: resistance rises as the conductor heats up. Use R at 70 °C for PVC insulation and 90 °C for XLPE. From the 20 °C value: copper R₇₀ = R₂₀ × 1.196 and R₉₀ = R₂₀ × 1.275.
  • AC vs DC: for cables up to about 50 mm² they are practically equal. For large cables, use the manufacturer's AC resistance — skin and proximity effects add a few percent.
  • Source: IEC 60228 gives maximum conductor resistance at 20 °C for every size. See the cable resistance table, and confirm with the approved manufacturer's datasheet.

05Worked example: 4 mm² vs 6 mm²

Single-phase load of 25 A, 230 V, power factor 0.9, one-way length 50 m, copper cable with PVC insulation, limit 5%.

CableR at 70 °C (Ω/km)ΔVΔV%Result
4 mm² Cu/PVC5.5212.53 V5.45%FAIL
6 mm² Cu/PVC3.698.41 V3.66%PASS

Working for 4 mm²: ΔV = 2 × 25 × 0.050 × (5.52 × 0.9 + 0.1 × 0.436) = 12.53 V → 12.53 ÷ 230 = 5.45%. The 4 mm² cable can carry 25 A, but over 50 m it fails the voltage drop check; 6 mm² passes.

06Step-by-step approach

  1. Confirm the load current and operating power factor.
  2. Obtain R and X at operating temperature from the selected cable manufacturer's data.
  3. Calculate the voltage drop and express it as a percentage of nominal voltage.
  4. Compare with the project limit; if it fails, increase the cable size or shorten the route.
  5. Check the cumulative drop from the origin (feeder + sub-main + final circuit).
Engineering caution: Voltage drop alone does not determine cable size. Also verify current-carrying capacity, derating, short-circuit withstand, protective-device coordination, disconnection requirements, harmonics where relevant, installation method and termination limits.

07Use the free calculator

The voltage drop calculator now has a cable preset: choose copper or aluminium, PVC or XLPE and the cable size, and R and X fill in automatically. Each result shows a green PASS or red FAIL against a 3% or 5% limit.

08Try it: lighting circuit voltage drop

FAQFrequently asked questions

What is the maximum allowed voltage drop?

A widely used reference is IEC 60364-5-52 (Annex G): 3% for lighting and 5% for other uses when the installation is supplied directly from a public low-voltage network, and 6% / 8% when it is supplied from a private LV supply (own transformer). Always follow the project specification and the local utility rules, which may be stricter.

Why do we multiply by 2 for single-phase voltage drop?

Current flows out on the line conductor and returns on the neutral, so it travels the route length twice. The single-phase formula uses 2 × I × L, where L is the one-way length. Balanced three-phase circuits use √3 instead.

Should I use AC or DC resistance?

Use the conductor resistance at its operating temperature (70 °C for PVC, 90 °C for XLPE). For small cables (up to about 50 mm²) AC and DC resistance are practically the same. For large cables the AC resistance is higher because of skin and proximity effects, so take the AC value from the manufacturer's datasheet.

Is the reactance X important?

For small cables X (about 0.08–0.1 Ω/km) is tiny compared with R, so it hardly changes the result. For large cables R becomes small and X starts to matter, especially at lower power factors.

If a cable passes voltage drop, is it the correct size?

Not necessarily. Also check current-carrying capacity with derating, short-circuit withstand, protective device coordination, disconnection times, harmonics and termination limits. Voltage drop is one of several checks.