American Wire Gauge (AWG) sizes appear on US-standard equipment, control wiring and many datasheets. This converter gives the exact cross-section in mm² and the nearest IEC metric size that is equal or larger.
01AWG to mm² table
| AWG | Area (mm²) | Diameter (mm, solid) | Nearest IEC size ≥ |
|---|---|---|---|
| 18 AWG | 0.82 | 1.02 | 1 mm² |
| 16 AWG | 1.31 | 1.29 | 1.5 mm² |
| 14 AWG | 2.08 | 1.63 | 2.5 mm² |
| 12 AWG | 3.31 | 2.05 | 4 mm² |
| 10 AWG | 5.26 | 2.59 | 6 mm² |
| 8 AWG | 8.37 | 3.26 | 10 mm² |
| 6 AWG | 13.30 | 4.12 | 16 mm² |
| 4 AWG | 21.15 | 5.19 | 25 mm² |
| 3 AWG | 26.67 | 5.83 | 35 mm² |
| 2 AWG | 33.63 | 6.54 | 35 mm² |
| 1 AWG | 42.41 | 7.35 | 50 mm² |
| 1/0 AWG | 53.48 | 8.25 | 70 mm² |
| 2/0 AWG | 67.43 | 9.27 | 70 mm² |
| 3/0 AWG | 85.03 | 10.40 | 95 mm² |
| 4/0 AWG | 107.22 | 11.68 | 120 mm² |
02Formula
Diameter d = 0.127 mm × 92(36 − n)/39 · Area = π/4 × d²
For 1/0, 2/0, 3/0, 4/0 use n = 0, −1, −2, −3.
For 1/0, 2/0, 3/0, 4/0 use n = 0, −1, −2, −3.
03Practical notes
- AWG and metric sizes are not exact equivalents; when substituting, choose the metric size that is equal or larger and re-check current rating, voltage drop and terminal size.
- Larger conductors are specified in kcmil (1 kcmil = 0.5067 mm²); 250 kcmil ≈ 127 mm².
- Current ratings differ between NEC and IEC methods — always use the rating table for the standard your project follows.
FAQFrequently asked questions
What is 12 AWG in mm²?
12 AWG is 3.31 mm². The nearest IEC size that is equal or larger is 4 mm².
What is 10 AWG in mm²?
10 AWG is 5.26 mm²; the nearest larger IEC size is 6 mm².
What is 4/0 AWG in mm²?
4/0 AWG is 107.2 mm²; the nearest larger IEC size is 120 mm².
Is 2.5 mm² the same as 14 AWG?
Close but not identical: 14 AWG is 2.08 mm², so 2.5 mm² is slightly larger.