The capacitor bank rating needed to raise the power factor from cos φ₁ to cos φ₂ is Q = P × (tan φ₁ − tan φ₂), where P is the active power in kW. The table gives the multiplier (tan φ₁ − tan φ₂); multiply it by the load kW to get kVAR.
01kVAR multiplier table
Rows: existing power factor. Columns: target power factor. kVAR = kW × multiplier.
| Existing PF | → 0.90 | → 0.92 | → 0.95 | → 0.98 | → 1.00 |
|---|---|---|---|---|---|
| 0.50 | 1.248 | 1.306 | 1.403 | 1.529 | 1.732 |
| 0.55 | 1.034 | 1.092 | 1.190 | 1.315 | 1.518 |
| 0.60 | 0.849 | 0.907 | 1.005 | 1.130 | 1.333 |
| 0.65 | 0.685 | 0.743 | 0.840 | 0.966 | 1.169 |
| 0.70 | 0.536 | 0.594 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.398 | 0.456 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.266 | 0.324 | 0.421 | 0.547 | 0.750 |
| 0.82 | 0.214 | 0.272 | 0.369 | 0.495 | 0.698 |
| 0.85 | 0.135 | 0.194 | 0.291 | 0.417 | 0.620 |
| 0.88 | 0.055 | 0.114 | 0.211 | 0.337 | 0.540 |
| 0.90 | — | 0.058 | 0.156 | 0.281 | 0.484 |
| 0.92 | — | — | 0.097 | 0.223 | 0.426 |
02Worked example
multiplier = tan(cos⁻¹0.80) − tan(cos⁻¹0.95) = 0.750 − 0.329 = 0.421
Q = 500 × 0.421 = 210 kVAR → choose the next standard bank size (for example 225 or 250 kVAR in steps).
03Practical notes
- Avoid over-correction (leading power factor) at light load — use an automatic stepped bank with a power factor controller.
- Where harmonics are present (drives, UPS, LED drivers), use detuned banks with reactors; check resonance.
- Capacitor kVAR is rated at its nominal voltage; output varies with the square of the applied voltage.
- The utility tariff and project specification set the required target power factor.
FAQFrequently asked questions
How do I calculate kVAR for power factor correction?
kVAR = kW × (tan φ₁ − tan φ₂), where φ₁ = cos⁻¹(existing PF) and φ₂ = cos⁻¹(target PF). Example: 500 kW from 0.80 to 0.95 needs about 210 kVAR.
What is the multiplier to correct power factor from 0.8 to 0.95?
0.421. Multiply the load in kW by 0.421 to get the capacitor kVAR.
Can I correct the power factor to 1.0?
In theory yes, but in practice a target of 0.95–0.98 is usual. Correcting to unity risks a leading power factor at light load and resonance with harmonics.
Why use an automatic capacitor bank?
Load changes through the day. An automatic stepped bank with a controller switches steps in and out to keep the power factor near the target without over-correcting.