REFERENCE · TRANSFORMERS

Transformer full-load current table (kVA to amps)

Three-phase transformer full-load current from 25 to 3150 kVA at 400 V, 415 V, 11 kV, 13.8 kV and 33 kV, with an instant kVA-to-amps calculator and worked example.

4 min readUpdated 22 Nov 2026Department: Transformers
Transformers

Full-load current of a three-phase transformer: I = kVA × 1000 ÷ (√3 × V), where V is the line-to-line voltage. Use it for preliminary sizing of LV incomers, MV cables, CTs and protection settings.

01Full-load current table (A)

Rating400 V415 V11 kV13.8 kV33 kV
25 kVA36.134.81.31.00.44
50 kVA72.269.62.62.10.87
100 kVA1441395.24.21.7
160 kVA2312238.46.72.8
200 kVA28927810.58.43.5
250 kVA36134813.110.54.4
315 kVA45543816.513.25.5
400 kVA57755621.016.77.0
500 kVA72269626.220.98.7
630 kVA90987633.126.411.0
800 kVA1,1551,11342.033.514.0
1000 kVA1,4431,39152.541.817.5
1250 kVA1,8041,73965.652.321.9
1500 kVA2,1652,08778.762.826.2
1600 kVA2,3092,22684.066.928.0
2000 kVA2,8872,78210583.735.0
2500 kVA3,6083,47813110543.7
3150 kVA4,5474,38216513255.1

02Formula and worked example

I = S ÷ (√3 × V)
1000 kVA at 400 V: 1,000,000 ÷ (1.732 × 400) = 1,443 A
1000 kVA at 13.8 kV: 1,000,000 ÷ (1.732 × 13,800) = 41.8 A

03Using these values

  • These are rated (full-load) currents at nominal voltage. Actual load current depends on demand and power factor.
  • LV incomer breakers are usually selected at or just above the full-load current (for example 1600 A for a 1000 kVA, 400 V transformer), subject to the project design and coordination study.
  • Short-circuit current is a separate calculation using the transformer impedance (Uk%). Use the calculator centre for fault level.

FAQFrequently asked questions

What is the full load current of a 1000 kVA transformer?

About 1,443 A at 400 V, 1,391 A at 415 V, 52.5 A at 11 kV and 41.8 A at 13.8 kV, using I = kVA × 1000 ÷ (√3 × V).

What is the full load current of a 500 kVA transformer at 400 V?

About 722 A (500,000 ÷ (1.732 × 400)).

How do I calculate transformer full load current?

Divide the rating in VA by √3 times the line-to-line voltage: I = S ÷ (√3 × V). For single-phase transformers use I = S ÷ V.

Is full load current the same as short-circuit current?

No. Short-circuit current is much higher and depends on the transformer impedance: roughly I_sc ≈ I_FL × 100 ÷ Uk%. For a 1000 kVA, 400 V transformer with 6% impedance that is about 24 kA (ignoring the source impedance).