Full-load current of a three-phase transformer: I = kVA × 1000 ÷ (√3 × V), where V is the line-to-line voltage. Use it for preliminary sizing of LV incomers, MV cables, CTs and protection settings.
01Full-load current table (A)
| Rating | 400 V | 415 V | 11 kV | 13.8 kV | 33 kV |
|---|---|---|---|---|---|
| 25 kVA | 36.1 | 34.8 | 1.3 | 1.0 | 0.44 |
| 50 kVA | 72.2 | 69.6 | 2.6 | 2.1 | 0.87 |
| 100 kVA | 144 | 139 | 5.2 | 4.2 | 1.7 |
| 160 kVA | 231 | 223 | 8.4 | 6.7 | 2.8 |
| 200 kVA | 289 | 278 | 10.5 | 8.4 | 3.5 |
| 250 kVA | 361 | 348 | 13.1 | 10.5 | 4.4 |
| 315 kVA | 455 | 438 | 16.5 | 13.2 | 5.5 |
| 400 kVA | 577 | 556 | 21.0 | 16.7 | 7.0 |
| 500 kVA | 722 | 696 | 26.2 | 20.9 | 8.7 |
| 630 kVA | 909 | 876 | 33.1 | 26.4 | 11.0 |
| 800 kVA | 1,155 | 1,113 | 42.0 | 33.5 | 14.0 |
| 1000 kVA | 1,443 | 1,391 | 52.5 | 41.8 | 17.5 |
| 1250 kVA | 1,804 | 1,739 | 65.6 | 52.3 | 21.9 |
| 1500 kVA | 2,165 | 2,087 | 78.7 | 62.8 | 26.2 |
| 1600 kVA | 2,309 | 2,226 | 84.0 | 66.9 | 28.0 |
| 2000 kVA | 2,887 | 2,782 | 105 | 83.7 | 35.0 |
| 2500 kVA | 3,608 | 3,478 | 131 | 105 | 43.7 |
| 3150 kVA | 4,547 | 4,382 | 165 | 132 | 55.1 |
02Formula and worked example
1000 kVA at 400 V: 1,000,000 ÷ (1.732 × 400) = 1,443 A
1000 kVA at 13.8 kV: 1,000,000 ÷ (1.732 × 13,800) = 41.8 A
03Using these values
- These are rated (full-load) currents at nominal voltage. Actual load current depends on demand and power factor.
- LV incomer breakers are usually selected at or just above the full-load current (for example 1600 A for a 1000 kVA, 400 V transformer), subject to the project design and coordination study.
- Short-circuit current is a separate calculation using the transformer impedance (Uk%). Use the calculator centre for fault level.
FAQFrequently asked questions
What is the full load current of a 1000 kVA transformer?
About 1,443 A at 400 V, 1,391 A at 415 V, 52.5 A at 11 kV and 41.8 A at 13.8 kV, using I = kVA × 1000 ÷ (√3 × V).
What is the full load current of a 500 kVA transformer at 400 V?
About 722 A (500,000 ÷ (1.732 × 400)).
How do I calculate transformer full load current?
Divide the rating in VA by √3 times the line-to-line voltage: I = S ÷ (√3 × V). For single-phase transformers use I = S ÷ V.
Is full load current the same as short-circuit current?
No. Short-circuit current is much higher and depends on the transformer impedance: roughly I_sc ≈ I_FL × 100 ÷ Uk%. For a 1000 kVA, 400 V transformer with 6% impedance that is about 24 kA (ignoring the source impedance).