REFERENCE · CABLE DATA

Cable resistance table: copper and aluminium (Ω/km)

Copper and aluminium cable conductor resistance in Ω/km from 1.5 to 300 mm² at 20 °C (IEC 60228), 70 °C (PVC) and 90 °C (XLPE), with an interactive size finder and temperature correction formula.

4 min readUpdated 21 Nov 2026Department: Cables & Jointing
Cables & Jointing

Conductor resistance in Ω/km for stranded copper and aluminium conductors, based on the maximum DC resistance at 20 °C in IEC 60228 and corrected to typical operating temperatures: 70 °C for PVC and 90 °C for XLPE insulation.

01Copper conductor resistance (Ω/km)

Size20 °C (IEC 60228 max)70 °C (PVC)90 °C (XLPE)
1.5 mm²12.1014.4815.43
2.5 mm²7.418.879.45
4 mm²4.615.525.88
6 mm²3.083.693.93
10 mm²1.832.192.33
16 mm²1.151.381.47
25 mm²0.7270.8700.927
35 mm²0.5240.6270.668
50 mm²0.3870.4630.493
70 mm²0.2680.3210.342
95 mm²0.1930.2310.246
120 mm²0.1530.1830.195
150 mm²0.1240.1480.158
185 mm²0.09910.1190.126
240 mm²0.07540.09020.0961
300 mm²0.06010.07190.0766

02Aluminium conductor resistance (Ω/km)

Size20 °C (IEC 60228 max)70 °C (PVC)90 °C (XLPE)
16 mm²1.912.302.45
25 mm²1.201.441.54
35 mm²0.8681.041.11
50 mm²0.6410.7700.822
70 mm²0.4430.5320.568
95 mm²0.3200.3850.410
120 mm²0.2530.3040.324
150 mm²0.2060.2480.264
185 mm²0.1640.1970.210
240 mm²0.1250.1500.160
300 mm²0.1000.1200.128

03Temperature correction

Copper: RT = R20 × (234.5 + T) ÷ 254.5 → × 1.196 at 70 °C, × 1.275 at 90 °C
Aluminium: RT = R20 × (228 + T) ÷ 248 → × 1.202 at 70 °C, × 1.282 at 90 °C

04Using these values

  • For voltage drop, use R at the conductor's operating temperature — or pick the size in the voltage drop calculator and it fills R and X for you.
  • IEC 60228 values are maximums; a real cable's datasheet may show the same or slightly lower resistance.
  • For cables above about 150 mm², use the manufacturer's AC resistance (skin and proximity effects).
  • Reactance X for typical LV multicore cables is about 0.08–0.10 Ω/km.

FAQFrequently asked questions

What is the resistance of 4 mm² copper cable?

IEC 60228 gives a maximum of 4.61 Ω/km at 20 °C for a 4 mm² stranded copper conductor. Corrected to operating temperature it is about 5.52 Ω/km at 70 °C (PVC) and 5.88 Ω/km at 90 °C (XLPE).

What is the resistance of 6 mm² copper cable?

3.08 Ω/km at 20 °C (IEC 60228 maximum), about 3.69 Ω/km at 70 °C and 3.93 Ω/km at 90 °C.

How do I convert cable resistance from 20 °C to 70 °C or 90 °C?

For copper multiply by (234.5 + T) ÷ 254.5: × 1.196 for 70 °C and × 1.275 for 90 °C. For aluminium multiply by (228 + T) ÷ 248: × 1.202 for 70 °C and × 1.282 for 90 °C.

How much higher is aluminium resistance than copper?

For the same cross-section, aluminium has roughly 1.6 times the resistance of copper, which is why aluminium cables are usually one or two sizes larger for the same duty.

Are these AC or DC resistance values?

They are DC values from IEC 60228, corrected for temperature. For small cables they are practically equal to AC resistance. For large cables use the manufacturer's AC resistance, which is a few percent higher.