Conductor resistance in Ω/km for stranded copper and aluminium conductors, based on the maximum DC resistance at 20 °C in IEC 60228 and corrected to typical operating temperatures: 70 °C for PVC and 90 °C for XLPE insulation.
01Copper conductor resistance (Ω/km)
| Size | 20 °C (IEC 60228 max) | 70 °C (PVC) | 90 °C (XLPE) |
|---|---|---|---|
| 1.5 mm² | 12.10 | 14.48 | 15.43 |
| 2.5 mm² | 7.41 | 8.87 | 9.45 |
| 4 mm² | 4.61 | 5.52 | 5.88 |
| 6 mm² | 3.08 | 3.69 | 3.93 |
| 10 mm² | 1.83 | 2.19 | 2.33 |
| 16 mm² | 1.15 | 1.38 | 1.47 |
| 25 mm² | 0.727 | 0.870 | 0.927 |
| 35 mm² | 0.524 | 0.627 | 0.668 |
| 50 mm² | 0.387 | 0.463 | 0.493 |
| 70 mm² | 0.268 | 0.321 | 0.342 |
| 95 mm² | 0.193 | 0.231 | 0.246 |
| 120 mm² | 0.153 | 0.183 | 0.195 |
| 150 mm² | 0.124 | 0.148 | 0.158 |
| 185 mm² | 0.0991 | 0.119 | 0.126 |
| 240 mm² | 0.0754 | 0.0902 | 0.0961 |
| 300 mm² | 0.0601 | 0.0719 | 0.0766 |
02Aluminium conductor resistance (Ω/km)
| Size | 20 °C (IEC 60228 max) | 70 °C (PVC) | 90 °C (XLPE) |
|---|---|---|---|
| 16 mm² | 1.91 | 2.30 | 2.45 |
| 25 mm² | 1.20 | 1.44 | 1.54 |
| 35 mm² | 0.868 | 1.04 | 1.11 |
| 50 mm² | 0.641 | 0.770 | 0.822 |
| 70 mm² | 0.443 | 0.532 | 0.568 |
| 95 mm² | 0.320 | 0.385 | 0.410 |
| 120 mm² | 0.253 | 0.304 | 0.324 |
| 150 mm² | 0.206 | 0.248 | 0.264 |
| 185 mm² | 0.164 | 0.197 | 0.210 |
| 240 mm² | 0.125 | 0.150 | 0.160 |
| 300 mm² | 0.100 | 0.120 | 0.128 |
03Temperature correction
Aluminium: RT = R20 × (228 + T) ÷ 248 → × 1.202 at 70 °C, × 1.282 at 90 °C
04Using these values
- For voltage drop, use R at the conductor's operating temperature — or pick the size in the voltage drop calculator and it fills R and X for you.
- IEC 60228 values are maximums; a real cable's datasheet may show the same or slightly lower resistance.
- For cables above about 150 mm², use the manufacturer's AC resistance (skin and proximity effects).
- Reactance X for typical LV multicore cables is about 0.08–0.10 Ω/km.
FAQFrequently asked questions
What is the resistance of 4 mm² copper cable?
IEC 60228 gives a maximum of 4.61 Ω/km at 20 °C for a 4 mm² stranded copper conductor. Corrected to operating temperature it is about 5.52 Ω/km at 70 °C (PVC) and 5.88 Ω/km at 90 °C (XLPE).
What is the resistance of 6 mm² copper cable?
3.08 Ω/km at 20 °C (IEC 60228 maximum), about 3.69 Ω/km at 70 °C and 3.93 Ω/km at 90 °C.
How do I convert cable resistance from 20 °C to 70 °C or 90 °C?
For copper multiply by (234.5 + T) ÷ 254.5: × 1.196 for 70 °C and × 1.275 for 90 °C. For aluminium multiply by (228 + T) ÷ 248: × 1.202 for 70 °C and × 1.282 for 90 °C.
How much higher is aluminium resistance than copper?
For the same cross-section, aluminium has roughly 1.6 times the resistance of copper, which is why aluminium cables are usually one or two sizes larger for the same duty.
Are these AC or DC resistance values?
They are DC values from IEC 60228, corrected for temperature. For small cables they are practically equal to AC resistance. For large cables use the manufacturer's AC resistance, which is a few percent higher.