Mini design project
Villa electrical design
Load list → demand → phase balancing → 20 circuits, MCBs, cables and RCDs → 63 A main board and SLD.
Teaching project. A complete preliminary design method with typical values — not a design to build from.
The brief
A two-storey villa with a majlis, kitchen, six bedrooms, laundry, outdoor lighting, a water pump and six split air-conditioning units. Supply is 230/400 V, three-phase, four-wire from the utility meter. Design the main distribution board: circuits, protective devices, cables, RCD protection and the incoming rating.
This is a teaching example. Demand factors, MCB ratings and cable sizes are typical starting points, not rules. The utility's requirements, the applicable wiring standard, cable manufacturer data and the local authority's rules govern a real design.
Step 1 — List every load
Each appliance group is a circuit. Air-conditioning units and water heaters get their own circuits because they run for long periods at full load.
Step 2 — Apply demand factors
Not every socket is used at full rating at the same time, but in a hot climate all AC units can run together, so they keep a demand factor of 1.0.
P = 32.3 kW Q = 10.9 kvar S = √(P² + Q²) = 34.1 kVA
Step 3 — Balance the phases
Circuits are allocated largest first to the least-loaded phase:
| Phase | Demand kVA | Current |
|---|---|---|
| L1 | 11.41 | 49.6 A |
| L2 | 11.84 | 51.5 A |
| L3 | 11.36 | 49.4 A |
Step 4 — Circuit schedule
| Circuit | Connected kW | DF | Design current Ib | MCB | Cable | RCD | Phase |
|---|---|---|---|---|---|---|---|
| Lighting — ground floor | 0.8 | 0.9 | 3.7 A | B10 | 1.5 mm² | — | L3 |
| Lighting — first floor | 0.8 | 0.9 | 3.7 A | B10 | 1.5 mm² | — | L1 |
| Lighting — outdoor | 0.5 | 1.0 | 2.3 A | B10 | 1.5 mm² | 30 mA | L2 |
| Sockets — living / majlis | 2.0 | 0.4 | 9.2 A | B16 | 2.5 mm² | 30 mA | L2 |
| Sockets — bedrooms GF | 2.0 | 0.4 | 9.2 A | B16 | 2.5 mm² | 30 mA | L3 |
| Sockets — bedrooms FF | 2.0 | 0.4 | 9.2 A | B16 | 2.5 mm² | 30 mA | L2 |
| Sockets — kitchen 1 | 3.0 | 0.5 | 13.7 A | B20 | 4 mm² | 30 mA | L3 |
| Sockets — kitchen 2 | 3.0 | 0.5 | 13.7 A | B20 | 4 mm² | 30 mA | L1 |
| Cooker | 7.0 | 0.6 | 30.4 A | B32 | 6 mm² | — | L1 |
| Laundry | 3.0 | 0.5 | 13.7 A | B20 | 4 mm² | 30 mA | L3 |
| Water heater 1 | 1.5 | 0.7 | 6.5 A | B16 | 2.5 mm² | 30 mA | L1 |
| Water heater 2 | 1.5 | 0.7 | 6.5 A | B16 | 2.5 mm² | 30 mA | L3 |
| Water heater 3 | 1.5 | 0.7 | 6.5 A | B16 | 2.5 mm² | 30 mA | L1 |
| Split AC unit 1 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L2 |
| Split AC unit 2 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L3 |
| Split AC unit 3 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L2 |
| Split AC unit 4 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L3 |
| Split AC unit 5 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L1 |
| Split AC unit 6 | 2.5 | 1.0 | 12.1 A | C16 | 2.5 mm² | — | L2 |
| Water pump | 1.1 | 1.0 | 5.6 A | C10 | 2.5 mm² | 30 mA | L2 |
| Total | 44.7 |
Check each line: Ib ≤ In ≤ Iz for the actual installation method, voltage drop to the furthest point, and earth-fault loop impedance for the MCB curve. AC compressors and pumps use C-curve devices to ride through starting current.
Step 5 — Main incoming device and cable
The most-loaded phase carries about 51 A. Allowing about 15 % margin gives 59 A → 63 A main device (4-pole, isolating the neutral), with a surge protective device. The incoming cable must have Iz ≥ 63 A after derating, acceptable voltage drop over the actual route, and be coordinated with the utility's meter and cut-out rating.
Step 6 — Earthing and RCD protection
Villa protection checklist
0 / 6Try it yourself
Change the loads and rebuild the board in the SLD builder, size the cables with the cable sizing assistant and estimate quantities with the quantity estimator.