Engineering glossary
Short definitions of terms and abbreviations used across the departments, guides and calculators.
- ACB
- Air circuit breaker — large LV breaker typically used as transformer incomer or main feeder device.
- Adiabatic equation
- S = √(I²t)/k; estimates minimum conductor size to withstand a short-circuit without exceeding its final temperature.
- ATS
- Automatic transfer switch — transfers load between normal and standby supplies.
- Bonding (protective equipotential)
- Connecting conductive parts together so they stay at similar potential during a fault.
- Buchholz relay
- Gas/oil-surge protection device fitted between tank and conservator on conservator-type transformers.
- Cascading
- Use of an upstream current-limiting device to allow a downstream device of lower breaking capacity, for manufacturer-tested combinations.
- CPC
- Circuit protective conductor — connects exposed-conductive-parts to the main earthing terminal.
- CT
- Current transformer — scales primary current down for protection and metering.
- DAR
- Dielectric absorption ratio — IR at 60 s divided by IR at 30 s.
- Demand factor
- Ratio of maximum demand to connected load for a group of loads.
- Differential protection (87)
- Unit protection comparing currents entering and leaving a protected zone.
- DMZ
- Demilitarised zone — network segment that brokers data between IT and OT networks.
- Dyn11
- Transformer vector group: HV delta, LV star with neutral; clock 11 = 330° lag, i.e. LV leads HV by 30°.
- Earth electrode
- Conductive part in contact with the earth, such as a rod, tape, plate or grid.
- EPR / GPR
- Earth (ground) potential rise — rise of earthing-system potential during an earth fault.
- FAT / SAT
- Factory and site acceptance tests of equipment and control systems.
- Feeder pillar
- Outdoor enclosure with protection, control and metering for street lighting or LV distribution circuits.
- FPI
- Fault passage indicator — shows whether fault current passed through an MV circuit.
- Grading margin
- Time difference between operation of upstream and downstream protection at a given fault current.
- IAC
- Internal arc classification of MV switchgear, describing personnel protection during an internal arc.
- Icu / Ics
- Ultimate and service short-circuit breaking capacities of an LV circuit breaker.
- Icw
- Rated short-time withstand current (with duration) of switchgear or an assembly.
- IDMT
- Inverse definite minimum time — overcurrent characteristic that operates faster at higher currents.
- IED
- Intelligent electronic device — microprocessor-based protection/control device.
- Insulation resistance (IR)
- Resistance of insulation measured with a DC test voltage.
- ITP
- Inspection and test plan listing inspections, tests, criteria, records and hold/witness points.
- LBS
- Load-break switch — can make and break load current but not interrupt fault current.
- Loop check
- Verification of an instrument or control signal from field device to control system and HMI.
- MCC
- Motor control centre — assembly of motor starters and feeders.
- MET
- Main earthing terminal — where earthing, protective and bonding conductors connect.
- MIR / WIR
- Material and work inspection requests used to call for inspection on site.
- NCR
- Non-conformance report — records work or material that does not meet requirements.
- NOP
- Normally-open point — the open switch that splits an MV ring into two radial feeders.
- ONAN
- Transformer cooling code: oil natural, air natural.
- PEN
- Combined protective earth and neutral conductor (TN-C portions of a system).
- PI
- Polarisation index — IR at 10 minutes divided by IR at 1 minute.
- PLC
- Programmable logic controller.
- Power factor
- Ratio of active power to apparent power (cos φ for sinusoidal conditions).
- RCD
- Residual current device — detects imbalance between line and neutral currents (earth leakage).
- REF
- Restricted earth-fault protection for transformer windings.
- RFI
- Request for information — formal query to the designer.
- RMU
- Ring main unit — compact MV switchgear for ring networks.
- SCADA
- Supervisory control and data acquisition.
- Selectivity (discrimination)
- Coordination so that only the protective device nearest a fault operates.
- SLD
- Single-line diagram representing a three-phase system with one line per circuit.
- Soft starter
- Thyristor-based reduced-voltage motor starter.
- Step / touch voltage
- Voltages experienced between feet, or between hand and feet, during an earth fault.
- TMS
- Time multiplier setting of an IDMT relay.
- TN-C-S / TN-S / TT
- LV system earthing arrangements describing source and exposed-part earthing.
- VFD
- Variable frequency drive — controls motor speed by varying supply frequency and voltage.
- VLF test
- Very-low-frequency AC withstand/diagnostic test used on MV cables.
- VPIS
- Voltage presence indicating system on MV switchgear (indication only).
- Z% (impedance voltage)
- Transformer short-circuit impedance as a percentage; governs fault level and regulation.