A structured overview of the key checks when reviewing an LV moulded-case circuit breaker. This guide provides a structured field and engineering review framework. Apply the sequence to the approved scope and record project-specific requirements separately.
01Rated current and frame
Distinguish frame size, rated current, adjustable trip setting and actual load current. Confirm ambient and enclosure conditions and manufacturer derating.
02Breaking capacity
Compare the breaker interrupting rating with the prospective short-circuit current at the installation point, using the relevant voltage and standard rating.
03Trip characteristics
Review long-time, short-time, instantaneous and earth-fault functions where provided. Settings must coordinate with downstream and upstream protection and conductor withstand.
04Selectivity and backup
Use manufacturer coordination tables and approved protection studies to assess discrimination and cascading/backup protection. Do not infer selectivity from breaker ampere ratings alone.
05Installation and verification
Check poles, accessories, shunt trip/undervoltage release, auxiliary contacts, cable/busbar terminations, enclosure and commissioning tests.