Troubleshooting flowchart
Breaker keeps tripping
An MCB, MCCB or ACB that trips repeatedly is telling you something. Find out what kind of trip it is before resetting again.
Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.
?Answer the questions
See the whole flowchart as a list
- Does it trip immediately when you close it, even with the loads switched off?
- Yes
- With the outgoing cable disconnected (isolated and proven dead first), does the breaker still trip on closing?
- Yes
- Suspect the breaker or its trip unit — A breaker that trips with nothing connected may have a faulty trip unit, mechanism, wrong setting or a shunt-trip/undervoltage circuit acting. Check settings and auxiliary trip circuits, then have the device tested or replaced per the manufacturer.
- No
- Fault on the outgoing circuit — Insulation-test the cable and connected equipment (phase-phase, phase-earth, neutral-earth). Sectionalise to find the faulty part. Do not re-close onto a suspected fault.
- Yes
- With the outgoing cable disconnected (isolated and proven dead first), does the breaker still trip on closing?
- No
- Does it trip only after running for a while (minutes or hours)?
- Yes
- Is the measured load current close to or above the breaker rating?
- Yes
- Genuine overload — The circuit carries more than it was designed for. Redistribute loads, check for added equipment, or re-design (larger breaker only if the cable and downstream equipment allow it — never upsize the breaker alone).
- No
- Heat at the breaker or a loose connection — Check terminal torque and look for discolouration; use thermography under load. High ambient in the panel or a hot neighbouring device can also cause thermal trips. Check panel ventilation and the device's temperature derating.
- Yes
- Is the measured load current close to or above the breaker rating?
- No
- Does it trip when a particular load starts (motor, transformer, large lighting group)?
- Yes
- Starting / inrush current — Inrush may exceed the instantaneous setting or MCB curve. Check the curve type (B/C/D) or MCCB instantaneous setting against the load's inrush, and verify the starting method of motors. Change settings only with a coordination review.
- No
- Is it an RCD/RCBO or does the trip indication show earth fault?
- Yes
- Earth leakage or earth fault — Follow the RCD flowchart: test insulation to earth, check for borrowed neutrals and look at cumulative leakage from electronic equipment.
- No
- Intermittent fault — Look for moisture, damaged cable, rodents, or a loose connection that arcs under vibration. Check event logs on electronic trip units for the trip type and current.
- Yes
- Is it an RCD/RCBO or does the trip indication show earth fault?
- Yes
- Does it trip when a particular load starts (motor, transformer, large lighting group)?
- Yes
- Does it trip only after running for a while (minutes or hours)?
- Yes
Related: Protection & Control department → · All flowcharts →