Troubleshooting flowchart
Low insulation resistance reading
An insulation reading below the acceptance criterion needs investigation before the circuit is energised.
Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.
?Answer the questions
See the whole flowchart as a list
- Was all equipment disconnected (drivers, electronics, surge devices, neutral link as required) and the cable ends clean and dry?
- Yes
- Is the low reading on one core only?
- Yes
- Is the cable new and not yet jointed?
- Yes
- Possible damage during installation — Inspect the route for damage points (pulling, sharp edges, trench). Check if water entered at an unsealed end. Use fault location if needed; replace the damaged section.
- No
- Suspect a joint or termination — Test each section separately by opening at joints/terminations to locate the fault. Re-make the defective joint following the kit instructions.
- Yes
- Is the cable new and not yet jointed?
- No
- Are all cores low by a similar amount?
- Yes
- Moisture or contamination likely — Check humidity and condensation; dry out where appropriate (heaters for panels/motors). Re-test and compare with the PI — it rises after drying if moisture was the cause.
- No
- Mixed results — test section by section — Separate the circuit into parts and test each to find which part pulls the reading down.
- Yes
- Are all cores low by a similar amount?
- Yes
- Is the low reading on one core only?
- No
- Re-test correctly — Connected electronics, SPDs or dirty terminations give false low readings. Disconnect them, clean and dry the ends, then repeat the test.
- Yes
Related: Testing & Commissioning department → · All flowcharts →