Troubleshooting flowchart

Low insulation resistance reading

An insulation reading below the acceptance criterion needs investigation before the circuit is energised.

Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.

?Answer the questions
    See the whole flowchart as a list
    • Was all equipment disconnected (drivers, electronics, surge devices, neutral link as required) and the cable ends clean and dry?
      • Yes
        • Is the low reading on one core only?
          • Yes
            • Is the cable new and not yet jointed?
              • Yes
                • Possible damage during installation — Inspect the route for damage points (pulling, sharp edges, trench). Check if water entered at an unsealed end. Use fault location if needed; replace the damaged section.
              • No
                • Suspect a joint or termination — Test each section separately by opening at joints/terminations to locate the fault. Re-make the defective joint following the kit instructions.
          • No
            • Are all cores low by a similar amount?
              • Yes
                • Moisture or contamination likely — Check humidity and condensation; dry out where appropriate (heaters for panels/motors). Re-test and compare with the PI — it rises after drying if moisture was the cause.
              • No
                • Mixed results — test section by section — Separate the circuit into parts and test each to find which part pulls the reading down.
      • No
        • Re-test correctly — Connected electronics, SPDs or dirty terminations give false low readings. Disconnect them, clean and dry the ends, then repeat the test.