Troubleshooting flowchart
Motor won't start
A motor that will not start may be a supply, control, protection or mechanical problem. Work from the supply towards the motor.
Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.
?Answer the questions
See the whole flowchart as a list
- Are all three supply voltages present and balanced at the starter/VFD input?
- Yes
- Does the contactor pull in (or the VFD show a run command) when you press start?
- Yes
- Does the motor hum but not turn?
- Yes
- Possible lost phase at the motor or a jammed load — Check voltage on all three phases at the motor terminals during start, and the output side of the contactor. If voltages are fine, check for a seized pump or bearing (with the motor isolated, try turning the shaft).
- No
- Does the overload or VFD trip immediately?
- Yes
- Overload/drive trip on start — Read the drive fault code or overload setting. Insulation-test the motor and cable (drive disconnected!). Check the overload setting matches the motor FLC and that the load isn't too heavy for the starting method.
- No
- Check output and motor circuit — Measure output voltage from the starter/VFD and continuity of the motor cable. Check the local isolator at the motor is closed and its auxiliary contact is not breaking the control circuit.
- Yes
- Does the overload or VFD trip immediately?
- Yes
- Does the motor hum but not turn?
- No
- Is there control voltage at the start circuit?
- Yes
- Are any interlocks open (emergency stop, local isolator aux, level switch, pressure switch, permissive from SCADA)?
- Yes
- Interlock preventing start — Identify which permissive is open and why (e.g. low-level cut-out protecting the pump from running dry). Do not bypass interlocks — fix the cause.
- No
- Fault in the control circuit — Trace the start circuit with the control drawing: start button, auto/manual selector, PLC output, contactor coil. A failed coil or PLC output is common.
- Yes
- Are any interlocks open (emergency stop, local isolator aux, level switch, pressure switch, permissive from SCADA)?
- No
- No control supply — Check the control transformer/fuse, control MCB and 24 V DC supply.
- Yes
- Is there control voltage at the start circuit?
- Yes
- Does the contactor pull in (or the VFD show a run command) when you press start?
- No
- Supply problem — Missing phase or low voltage: check upstream breaker, fuses and connections. Starting on two phases (single-phasing) will not produce rotation and overheats the motor.
- Yes