Troubleshooting flowchart
RCD nuisance tripping
RCDs trip when outgoing and returning current differ. Find where the 'missing' current goes.
Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.
?Answer the questions
See the whole flowchart as a list
- Does the RCD trip with all loads disconnected?
- Yes
- Does a test of the circuit insulation (dead, isolated) show low phase–earth or neutral–earth readings?
- Yes
- Earth fault in the wiring — Locate the fault by sectioning; neutral-earth faults are common and often only show up when loads are on.
- No
- Suspect the RCD — Test the RCD trip current and time with an RCD tester. Replace if out of tolerance.
- Yes
- Does a test of the circuit insulation (dead, isolated) show low phase–earth or neutral–earth readings?
- No
- Does it trip when a specific appliance is plugged in or switched on?
- Yes
- Faulty appliance — Test the appliance (insulation, protective conductor). Heating elements with moisture are common culprits.
- No
- Are there many electronic loads (LED drivers, IT, VFDs) on this RCD?
- Yes
- Cumulative leakage or switching inrush — Measure standing leakage with a leakage clamp. Split circuits between RCDs, follow manufacturer guidance on devices per RCD and consider RCD types suited to the load.
- No
- Does it trip in wet weather or after cleaning?
- Yes
- Moisture ingress — Check outdoor sockets, luminaires and junction boxes for water ingress and IP rating.
- No
- Borrowed neutral or N-E connection — Check that the circuit's neutral is not shared with another circuit and that neutral and earth are not connected downstream of the RCD.
- Yes
- Does it trip in wet weather or after cleaning?
- Yes
- Are there many electronic loads (LED drivers, IT, VFDs) on this RCD?
- Yes
- Does it trip when a specific appliance is plugged in or switched on?
- Yes
Related: Earthing & Bonding department → · All flowcharts →