Troubleshooting flowchart

Transformer temperature or Buchholz alarm

An alarm from transformer protection devices is a warning to act before the trip stage.

Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.

?Answer the questions
    See the whole flowchart as a list
    • Is it a Buchholz (gas) alarm?
      • Yes
        • Has the transformer recently been filled, topped up or energised for the first time?
          • Yes
            • Possibly trapped air — Air released after filling can collect in the relay. Follow the manufacturer's procedure to vent and analyse — do not assume; a gas sample analysis distinguishes air from fault gases.
          • No
            • Possible internal fault — escalate — Gas accumulation can indicate an internal fault. Reduce load or de-energise according to the site procedure, take a gas sample for analysis and involve the manufacturer/specialist before re-energising.
      • No
        • Is the load current above rated, or the ambient unusually high?
          • Yes
            • Thermal overload — Reduce load, check cooling (fans, radiator cleanliness, ventilation of the room) and compare with the loading guide for the actual ambient.
          • No
            • Do the temperature indicator and a thermographic check agree?
              • Yes
                • Cooling or internal issue — Inspect radiators, oil level, valves and fans. Abnormal temperature at normal load needs specialist investigation (oil test, DGA).
              • No
                • Instrument problem — Check the thermometer/WTI calibration, sensor pocket oil and wiring. Fix the indication but treat the alarm seriously until proven false.