Troubleshooting flowchart
Transformer temperature or Buchholz alarm
An alarm from transformer protection devices is a warning to act before the trip stage.
Fault-finding on electrical installations must be done by competent, authorised people under the site's safety rules. Isolate and prove dead before touching conductors; measurements on live equipment only with the right instruments, PPE and permission.
?Answer the questions
See the whole flowchart as a list
- Is it a Buchholz (gas) alarm?
- Yes
- Has the transformer recently been filled, topped up or energised for the first time?
- Yes
- Possibly trapped air — Air released after filling can collect in the relay. Follow the manufacturer's procedure to vent and analyse — do not assume; a gas sample analysis distinguishes air from fault gases.
- No
- Possible internal fault — escalate — Gas accumulation can indicate an internal fault. Reduce load or de-energise according to the site procedure, take a gas sample for analysis and involve the manufacturer/specialist before re-energising.
- Yes
- Has the transformer recently been filled, topped up or energised for the first time?
- No
- Is the load current above rated, or the ambient unusually high?
- Yes
- Thermal overload — Reduce load, check cooling (fans, radiator cleanliness, ventilation of the room) and compare with the loading guide for the actual ambient.
- No
- Do the temperature indicator and a thermographic check agree?
- Yes
- Cooling or internal issue — Inspect radiators, oil level, valves and fans. Abnormal temperature at normal load needs specialist investigation (oil test, DGA).
- No
- Instrument problem — Check the thermometer/WTI calibration, sensor pocket oil and wiring. Fix the indication but treat the alarm seriously until proven false.
- Yes
- Do the temperature indicator and a thermographic check agree?
- Yes
- Is the load current above rated, or the ambient unusually high?
- Yes
Related: Transformers department → · All flowcharts →