Worked example

LV sub-main cable selection

Ib ≤ In ≤ Iz, voltage drop and adiabatic check for a 180 A sub-main — with a candidate that fails.

Preliminary teaching example. Numbers show the method. They are not values to copy into a design.

180 Adesign current Ib
200 AMCCB setting In
201 Aderated cable rating Iz (120 mm²)
2.39 %voltage drop at full load

The brief

A 4-core copper XLPE/SWA cable feeds an SMDB 150 m from the MDB, on a cable tray grouped with other circuits, in a hot plant room. Design current is 180 A at 400 V, PF 0.85. The MCCB at the MDB is set at 200 A. The prospective fault at the MDB is 20 kA, cleared in 0.2 s or less. The project allows 4 % voltage drop for this sub-main.

Cable ratings, R and X values below are illustrative numbers for teaching only. Always use the manufacturer's data for the actual cable and the rating tables and correction factors for the actual installation method.

Step 1 — Current-carrying capacity

I_z = I_t × C_a × C_g × C_i
I_b ≤ I_n ≤ I_z

Correction factors used: ambient C_a = 0.91, grouping C_g = 0.85, other C_i = 1.0. Combined factor = 0.773.

Step 2 — Voltage drop

ΔV = √3 × I_b × L × (R cos φ + X sin φ)

For 120 mm²: ΔV = √3 × 180 × 0.15 × (0.196 × 0.85 + 0.072 × 0.527) = 9.56 V = 2.39 %.

Step 3 — Short-circuit withstand

S_min = √(I² t) ÷ k = √(20 000² × 0.2) ÷ 143 = 62.5 mm²

Step 4 — Compare the candidates

Candidate cables (illustrative data)
SizeIt (table)IzIn ≤ IzΔV≤ 4 %S minFault
95 mm²225 A174 A✗ Fail2.90 %✓ Pass63 mm²✓ Pass
120 mm²260 A201 A✓ Pass2.39 %✓ Pass63 mm²✓ Pass

The 95 mm² cable fails the overload check because grouping and ambient derating reduce its rating below the 200 A device setting. 120 mm² passes all three checks in this example — with little margin on Iz, so confirm the installation conditions before freezing the size.

Step 5 — Remaining checks

Complete before issuing the cable schedule

0 / 0
    Ticks are saved only in this browser. Adapt the list to the approved ITP and manufacturer instructions; it does not define acceptance criteria.