Worked example
Street lighting circuit design
Current per luminaire, distributed-load voltage drop with L1-L2-L3 rotation, and why rotation matters.
Preliminary teaching example. Numbers show the method. They are not values to copy into a design.
The brief
A road has 30 columns at 30 m spacing; the first column is 20 m from the feeder pillar, so the last is at 890 m. Each luminaire draws 150 W total input (including driver) at PF 0.95. The circuit is a 4-core 16 mm² Cu XLPE/SWA cable looped column to column, 230/400 V, with luminaires connected L1, L2, L3 in rotation.
Cable R and X (1.47 and 0.083 Ω/km) are illustrative. Use manufacturer data at operating temperature, the authority's voltage-drop limit and its column and cut-out details.
Step 1 — Current per luminaire
Each phase carries 10 luminaires — about 6.86 A at the pillar. Steady-state current is small: the protective device size is usually governed by LED driver inrush and the cable's protection, not by running current. Check the driver manufacturer's number of drivers per MCB curve.
Step 2 — Distributed-load voltage drop
The current in each cable section falls as luminaires are passed. The drop on each phase is the sum over sections of (current in section × section length × impedance). With balanced rotation the neutral current is close to zero, so only the phase conductor contributes.
| Phase | Luminaires | Current at pillar | ΔV | ΔV % of 230 V |
|---|---|---|---|---|
| L1 | 10 | 6.86 A | 4.15 V | 1.80 % |
| L2 | 10 | 6.86 A | 4.44 V | 1.93 % |
| L3 | 10 | 6.86 A | 4.74 V | 2.06 % |
Step 3 — Why rotation matters
If all 30 luminaires were connected to one phase, the same cable would carry all the current in the phase and the neutral. The drop at the end column would be about 26.66 V (11.59 %) — several times higher, plus a heavily loaded neutral and an unbalanced pillar.
Step 4 — Remaining checks
Street lighting circuit — before approval