This guide provides a structured engineering review approach. Use it with approved project documents, equipment manufacturer instructions and the applicable standards and authority requirements.
011. Understand the lighting design package
Review lighting layout, pole schedule, luminaire data sheets, photometric report, cable schedule, feeder pillar SLD, control philosophy and road/civil drawings. Confirm road classification, maintained illuminance or luminance criteria, uniformity and glare requirements from the project design basis. Pole spacing alone does not establish lighting compliance.
022. Feeder pillar and circuit architecture
Identify supply source, feeder pillar rating, incomer, outgoing protective devices, contactors, photocell/timer or control interface, surge protection where specified and spare capacity. Confirm circuit numbering and the normal control mode. Check the feeder pillar location, access, foundation, IP/IK requirements and earthing arrangement.
033. Cable route and pole connections
Trace each circuit through ducts, chambers, handholes and pole bases. Confirm cable type, cores, conductor size, route length, joints and termination details against approved schedules. Allowances for risers, tails and terminations should be based on the project measurement method, not an arbitrary blanket percentage. Protect cables at road crossings and entries as specified.
044. Pole and foundation interface
Check pole height, outreach, bracket arrangement, base plate, anchor bolts, orientation, foundation details and corrosion protection. Confirm handhole cover, terminal block, internal protective device if specified, cable gland and earth connection. Civil setting-out and electrical pole IDs must match the approved layout.
055. Luminaire and photometric data
Verify manufacturer/model, wattage, optical distribution, CCT, CRI, efficacy, driver, dimming/control interface, surge protection and environmental rating. Compare submitted photometric files and calculations with the specified road geometry, mounting height, tilt and spacing. A luminaire wattage match alone does not demonstrate photometric compliance.
066. Electrical calculations and protection
Check connected load, phase balancing, voltage drop, cable current capacity, short-circuit withstand, protective device characteristics and earth-fault/disconnection requirements. Consider driver inrush and harmonic characteristics where relevant. Verify calculations against the actual route and installation method.
077. Testing and commissioning
Inspect pole wiring, polarity, protective earth continuity, insulation resistance where appropriate, feeder pillar settings, control operation and circuit identification. Confirm photocell/timer settings, contactor operation, remote-control signals where fitted and night-time functional checks. Record defective luminaires and dark sections by pole ID.
088. Handover package
Provide as-built pole and circuit schedules, feeder pillar schedules, approved luminaire data, photometric reports, cable test records, earthing records, control settings, warranties and maintenance instructions. Update every changed pole or circuit ID in the final record.
09Circuit balancing and loading
For multi-phase lighting circuits, check how poles are distributed across phases and whether the phase allocation is reflected in the feeder schedule. Include actual luminaire driver input current and power factor data where required. Consider control gear inrush and the number of drivers switched simultaneously. A connected wattage total alone may not fully describe switching and protection behaviour.
10Route measurement and cable quantity
Distinguish route length from cable procurement length. The route may include horizontal distance, vertical risers, pole tails, feeder pillar entries, chamber slack and approved jointing allowances. Define the measurement convention and avoid double-counting shared route sections. Ensure the cable schedule and quantity take-off use the same route basis.
11Photometric verification
The calculation model must match the installed geometry: road width, pole setback, mounting height, outreach, tilt, spacing, carriageway arrangement and surface assumptions. Confirm the submitted IES/LDT file corresponds to the exact luminaire optic and output. If a pole position or luminaire model changes, assess whether the photometric calculation must be revised.
12Night inspection and maintenance
During night checks, record pole ID, circuit ID, observed output, flicker, orientation, dark spots and control response. Compare the observed installation against the approved lighting design and commissioning criteria. Ensure access covers are secured and that pole doors, glands and internal wiring remain protected against water ingress.
13Quick field review checklist
Before accepting or closing the work
- Coordinate lighting layout, pole schedule and photometric report
- Verify feeder pillar and control philosophy
- Trace cable route, pole IDs and termination details
- Check luminaire optical and electrical data
- Verify cable/protection/voltage-drop calculations
- Complete circuit tests and as-built records
14How to use this reference
Convert each relevant check into a project-specific inspection point. Identify the responsible person, approved reference, witness/hold point, acceptance criteria and required record. Where a requirement is not stated in the available project documents, raise a technical query rather than inventing a value or applying a generic limit.
Educational reference only. This page does not replace approved design calculations, manufacturer procedures, permit-to-work controls or statutory requirements.